Description
9229 9992 176 0D
29
2013-07-08
A further shunt release, transformer-operated release, undervoltage release or
instantaneous release can be installed as a 2nd release.
2nd shunt release (Y2) 3AX1101
Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104
The second shunt release Y2 is installed whenever more
than one shunt release is needed.
In this version, the electrical "off" command is passed by
means of a magnet armature to the "OPEN" latch by
release of an energy storage mechanism, thus switching
off the vacuum circuit-breaker. This tripping solenoid is
not designed for continuous operation. Any necessary
varistors and rectifiers are integrated in the release.
Power consumption is approximately 60 W / VA
Fig. 38
2. Shunt release (54.2)
The transformer-operated releases Y4, Y5 or Y6 consist
of an energy storage mechanism, an unlatching fixture
and an electromagnetic system. If the tripping current is
exceeded (90 % of the transformer-operated release's
rated current), the stored energy mechanism is
unlatched, thus initiating opening of the vacuum circuit-
breaker.
For use of the transformer-operated release, matching
transformers are also needed for matching, in addition to
the main current transformers.
Power consumption for 0.5 A and 1 A
≤
6 VA at
≤
90 %
of the transformer-operated release's rated current and
with open armature.
Fig. 39
Transformer-operated releases (54.3)
Summary of Contents for 3AH37
Page 4: ...4 9229 9992 176 0D 2013 07 08 Blank page ...
Page 50: ...Installation 50 9229 9992 176 0D 2013 07 08 Blank page ...
Page 54: ...Operation 54 9229 9992 176 0D 2013 07 08 Blank page ...
Page 60: ...Maintenance 60 9229 9992 176 0D 2013 07 08 Blank page ...
Page 62: ...Index of keywords 62 9229 9992 176 0D 2013 07 08 Blank page ...