Transport, storage and packing
12
9229 9947 176 0C
2013-03-28
Reusing the transport unit
Reusing the transport unit
To transport the vacuum circuit-breaker again, the pallet with carton or the case with
the most components can be reused.
Do not reuse severed tensioning straps or plastic wrap.
Pack the vacuum circuit-breaker in reverse order:
• Attach the vacuum circuit-breaker safely to the pallet using the appropriate
tools.
• Cover with foil and seal with adhesive tape.
• Attach accessories pack.
• Attach carton securely to the pallet base.
• Screw the wooden case back together.
• Before returning to the factory, ask the responsible Siemens representative for a
returned goods number (see also “Service”, on page 55).
• When returning a vacuum circuit-breaker, always indicate the type and serial
number (see “Rating plate”, on page 31).
Storage
* without carton
Note
Store the vacuum circuit-breaker in the following condition:
• OPEN position
• Closing spring relaxed
Note
Risk of corrosion damage if stored improperly!
If the storage conditions listed below are met, the vacuum circuit-breaker can be
stored for up to a year in its transport unit.
If the storage conditions are not met, the vacuum circuit-breaker cannot be stored
in the transport unit any longer than 6 months.
If storage of longer than one year is planned, unpack the vacuum circuit-breaker
from the transport unit. Further storage may necessitate fresh corrosion
protection, and it must be ensured that the vacuum circuit-breaker cannot be
damaged.
Storage room
Transport unit
Storage
time
Temperature
range
Comments
Number of
units per
stack
Enclosed, dry, well
ventilated and as
free from dust as
possible, with a
relative humidity of
less than 60 %.
unopened
max.
6 months
–40 °C to +55 °C
—
max. 4
unopened
max.
1 year
–5 °C to +40 °C
—
max. 4
open *
over 1 year
–5 °C to +40 °C
if necessary
with new
corrosion
protection
—