Installation
9229 9947 176 0C
41
2013-03-28
Earthing
Connecting to earth
Connect the vacuum circuit-breaker on the earth terminal (70.) to the high-voltage
protective earth as specified (DIN EN 50341).
• Fully unscrew hexagon socket head screw M12 with washer on the earth
terminal (70.).
• Tighten ring terminal of the earth wire with the M12 hexagon socket head screw
on the earth terminal (70.) with 40 Nm.
Connect low-voltage
Connect the low-voltage connecting cables in the customer's switch cabinet in such
a way that safe operation as per supplied circuit diagram is guaranteed.
Note
If the 3AH47 vacuum circuit-breaker is installed into a earthed metal frame and is
connected permanently and electrically conductive, no separate earthing needs
to be done.
Place serrated washers under the screw heads when fastening the vacuum
circuit-breaker in this case.
Fig. 55
Earth terminal
Fig. 56
Connecting earth wire