2.5 User test (device test)
The tests according to EN 60079-17 can be carried out together with
the user test. The device must be taken out of operation if the test
results are negative.
Initialization
•
The three phase currents running through the 3RB3 must be as
symmetrical as possible.
•
The phase currents must be
≥
80 % of the set current
I
e
.
•
The currents must flow at least for the time
t
1
before the test.
•
The phase currents must be at least the same size as the value for
the lower setting mark of the current setting.
Test implementation
During the test all the protective functions are still active. The test is
initiated by pressing the TEST button (see device test in operating
instructions).
After the TEST button has been pressed, the device must trip within the
following time periods:
Test evaluation
The user test is considered to be carried out successfully if:
•
the device trips within the maximum permissible time limit and
•
contact 95-96 has opened (not welded shut).
2.6 Additional safety instructions
2.7 Environmental conditions
Permissible ambient temperature range:
•
Storage / transport: –40 °C to +80 °C
•
Operation: –25 °C to +60 °C
This device is maintenance-free.
To meet the conditions of the warranty, you must observe the safety
and commissioning instructions and the operating instructions
3ZX1012-0RB30-1AA1 (S00/S0)
3ZX1012-0RB30-3AA1 (S2).
Further information about the 3RB30 / 3RB31 can be found in Siemens
Industrial Controls Catalog IC 10 or on the Internet:
http://support.automation.siemens.com
CAUTION
This test must be carried out by a specialist familiar with the
standards stated!
CLASS
5E
10E
20E
30E
t
1
[minutes]
3
5
10
15
Max. phase
CLASS
5E
CLASS
10E
CLASS
20E
CLASS
30E
% of I
e
[s] max.
[s] max.
[s] max.
[s] max.
100 %
8
15
29
43
90 %
16
31
61
92
80 %
31
61
122
183
NOTICE
Correct functioning of the device can only be guaranteed when
these two criteria are met.
CAUTION
3RB30 and 3RB31 are not designed for load-side operation on
frequency converters.
!
3. Safety data
Values in the safety and
commissioning instructions for
40 °C ambient temperature
plus 10 K due to self-heating
SIL
SIL 1
HFT
0
λ
safe
440 * 10
-9
1/h
λ
DD
105 * 10
-9
1/h
λ
DU
296 * 10
-9
1/h
SFF
65%
DC
26%
MTBF
130 years
PFD
avg (for 36 months)
< 1,0 * 10
-2
Architecture
1001
T1 value
(repeat test)
DIN EN 60079-17 Section 4.4
T
lifetime
20 years
4. Maintenance and repair
5. Warranty
6. Further information