Functions
6.11 Inputs
Motor starter (3RK1308‑0**00‑0CP0)
108
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Input
n action
Input n level
Input n signal
Operating
mode
Description
Motor CW
NO
n. ret./ret.
Manual local
mode
•
The motor starter must be in "manual local"
mode for these actions.
•
Motor CW: Switching the motor on or off
•
Motor CCW: Switching the motor on or off
•
Only allowed as a NO contact
•
n. ret. The input action is active while the
input signal is pending.
•
ret.: The action becomes active by means of
the rising edge of the input and remains
active regardless of the level. The action is
reset by the input action "Quick Stop" or
"group fault".
Motor CCW
(with reversing
starters only)
Quick Stop
NO/NC
n. ret./ret.
All
•
Motor is switched off direction-
independently without group fault.
•
"Quick Stop" takes priority over "Motor CW"
and "Motor CCW"
Quick Stop
clockwise
NO/NC
n. ret./ret.
All
•
Motor is switched off with "Motor CW"
without group fault.
•
"Quick Stop" takes priority over "Motor CW"
Quick Stop
counter-clockwise
NO/NC
n. ret./ret.
All
•
Motor is switched off with "Motor CCW"
without group fault.
•
"Quick Stop" takes priority over
"Motor CCW"
•
The action is only available for reversing
starters.
Trip RESET
NO
n. ret.
All
•
"Trip RESET" is triggered once.
•
"Trip RESET" is only possible as NO
contact.
Cold start
NO
n. ret.
All
Enables switch-on without main power. If the
main power supply is nevertheless present
(current flowing), an internal trip command is
generated.
For fail-safe motor starters as of firmware
version V1.2.0
Operational trip end
position CW
NO/NC
n. ret.
All
The motor is tripped regardless of the direction
of rotation (CW or CCW).
•
The motor can only be switched on with
"Motor CCW".
•
The parameter can only be implemented as
"non-retentive".
•
A group fault is not generated, but a
diagnostic message is set in data set 92.