Functions
6.24 Trip RESET
Motor
starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
125
6.24
Trip RESET
"Trip RESET" acknowledges all the errors/faults that are currently active and that can be
acknowledged. An error/fault can be acknowledged if its cause has been rectified or if it is no
longer present.
Trip RESET is triggered by:
●
Loading a valid parameterization
●
Remote RESET via PLC (PIQ bit 0.3 Trip RESET)
●
Remote RESET via input actions (if parameterized)
●
TEST/RESET button on the ET 200SP motor starter
●
Power-on reset (switching off and on again of the 24 V supply voltages on the device)
Note
TRIP RESET as input n signal
The "Trip Reset" action is only possible as an "input n signal" (non-retentive).