Alarms/diagnostic messages
8.3 Interrupts
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
169
Error type
channel
diagnostics
Fault text
Remedial measures
1083
h
(4227
dec
)
Switching element
overload
Switching element (switching contact, power semiconductor) too hot.
Check the ambient conditions linked to cooling. You might have to take
derating into consideration. Check the number of switching operations. Also
check whether the fan is working properly.
1084
h
(4228
dec
)
Electronics supply
voltage too low
The supply voltage is below the permissible value.
Remedy: Check the power supply (load measurement, voltage range)
1088
h
(4232
dec
)
No switching element
supply voltage
No supply voltage has been detected or the mechanical rotary interlock is not
in the READY position.
Remedy: Check the power supply to the switching elements and the cabling
or turn the mechanical rotary interlock to the READY position.
1095
h
(4245
dec
)
Parameter error
The module is not yet parameterized or is incorrectly parameterized or the
safety-related parameters have been rejected.
Remedy: Correct the parameterization.
1096
h
(4246
dec
)
Process image error
The process image output (PIQ) contains invalid control bit combinations
(e.g. control bits for clockwise and counter-clockwise set simultaneously).
Remedy: Check and correct the process image output (PIQ).
10A5
h
(4261
dec
)
Residual current
No current flow is detected in the motor feeder after an ON command.
Possible causes: Phase failure, fault in the motor winding, fuse in the device
defective
Remedy: Check the motor feeder (main circuit) and the motor. Clear the
short-circuit in the system and replace the device.
100A
h
(4106
dec
)
Test mode current flow Current is flowing in the motor feeder although the motor feeder is in test
mode or the test position. Possible causes: The main circuit is not interrupted
in test operation.
The cold start function of the ET 200SP motor starter is activated.
Remedy: Check the wiring or deactivate the cold start function
109D
h
(4253
dec
)
Input Action
A warning or trip signal is active on at least one input.
Remedy: Check the application.
109E
h
(4254
dec
)
Emergency end
position CW
The "CW" emergency end position has been passed.
Remedy: Check the end position of the drive.
001F
h
(31
dec
)
Channel temporarily
unavailable
Wait until the firmware update is completed.
109F
h
(4255
dec
)
Emergency trip end
position CCW
The "CCW" emergency end position has been passed.
Remedy: Check the end position of the drive.
134B
h
(4939
dec
)
Trip Reset not possible Trip reset is currently not possible (e.g. because the cooling phase is in
progress).
Remedy: Repeat the action later (e.g. after the cooling time has elapsed).