Data sets
A.10 DS94 Read measured values
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
191
A.10
DS94 Read measured values
Object
number
Byte.Bit
Coding
Meaning
Range of
values
Increment
User data (technology data)
Measured values (volatile)
504 0
Unsigned 8
Phase current I
L1(%)
0 ... 796 %
3.125 %
505 1
Unsigned 8
Phase current I
L2(%)
0 ... 796 %
3.125 %
506 2
Unsigned 8
Phase current I
L3(%)
0 ... 796 %
3.125 %
- 3 ... 6
0x00
Reserved
-
-
503 7
Unsigned 8
Unbalance
0 ... 255 %
1 %
502 8 ... 9
Unsigned 16
Motor heating
0 ... 1,000 %
1 %
518 10, 11
Switching element heating
0 ... 1,000 %
1 %
- 10 ... 27
0x00
Reserved
-
-
513 28 ... 31
Signed 32
Phase current I
L1(rms)
±0 ... 20,000 A 0.01 A
514 32 ... 35
Signed 32
Phase current I
L2(rms)
±0 ... 20,000 A 0.01 A
515 36 ... 39
Signed 32
Phase current I
L3(rms)
±0 ... 20,000 A 0.01 A
516 40 ... 41
Unsigned 16
Electronics supply voltage
0 ... 1,500 V
0.1 V
- 42 ... 63
0x00
Reserved
-
-