Data sets
A.15 Read DS204 device parameter 2
Motor starter (3RK1308‑0**00‑0CP0)
200
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
A.15
Read DS204 device parameter 2
DS204 contains the second part of the incorrect parameters with which the motor starter is
working.
The defaults appear in italics in the Value range column.
Object
number
Byte.Bit
Range of values
Meaning
See Chapter ...
18 0.0 - 0.3
1
… 7.5 s/0.5 s
[2 … 15]
Default value is [2]: 1 s.
Blocking time
Blocking time and blocking current
(Page 95)
- 0.4 - 0.7
[0]: Reserved
Reserved
-
2210 1
0 … 99 %/1 %
[0 … 99]
[0]:
Deactivated
Warning limit - motor heating Overload protection (Page 76)
- 2 - 3
[0]: Reserved
Reserved
-
- 4 - 5
[0]: Reserved
Reserved
-
17 6
150 ... 1500 %/50 %
[3 ... 20]
Default value is [16]:
800 %
As of firmware version
V1.2.0
Blocking current
Blocking time and blocking current
(Page 95)
- 7
[0]: Reserved
Reserved
-
2213 8
18.75 … 100 %/3.125 %
[6 … 32]
[0]: Deactivated
Default value is [7]:
21.875 %
Lower current warning limit
Upper/lower current warning limit
(Page 93)
2214 9
50 … 400 %/3.125 %
[16 … 128]
[0]: Deactivated
Default value is [36]:
112.5 %
Upper current warning limit
Upper/lower current warning limit
(Page 93)