Functions
6.16 Trip emergency end position CCW
Motor starter (3RK1308‑0**00‑0CP0)
116
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
6.16
Trip emergency end position CCW
If the motor control command is not equal to "Motor OFF", the diagnostic interrupt "Trip end
position CCW
responded" incoming is triggered when a 0 → 1 edge is detected at the digital
input. This diagnostic interrupt results in internal tripping of the motor when emergency start
is deactivated. The interrupt "Trip end position CCW" is reported as outgoing (entry 92 is
deleted) if the motor control command is "Motor OFF". If the motor control command
"Motor CCW" is issued in the case of trip limit CCW DI static "1", an incoming diagnostic
message "trip end position CCW" is triggered (only if the diagnostic message was already
outgoing or has been deleted). This diagnostic message prevents renewed switch-on of the
motor in the CCW direction of rotation (emergency start deactivated).
The action "Trip end position CCW" results in the following behavior:
●
The motor is tripped regardless of the direction of rotation (CW or CCW).
●
You can switch the motor back on again after deletion of the control command
"Motor CW/CCW".
●
The motor can only be switched on with "Motor CW".
●
The parameter can only be implemented as "non-retentive".
●
A group fault is generated and a diagnostics entry created.
●
Emergency trip end position CCW can be overridden by emergency starting.