Functions
6.23 Quick Stop counter-clockwise
Motor starter (3RK1308‑0**00‑0CP0)
124
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
6.23
Quick Stop counter-clockwise
The action "Quick Stop CCW" results in the following behavior:
●
The motor is switched off with pending signal "Motor CCW" without group fault
●
The motor is not switched off with pending signal "Motor CW"
●
"Quick Stop CCW" takes priority over "Motor CCW"
●
The input action responds to the active edge of the input signal, Deactivation is possible
when the static input signal "Quick Stop" is present.
●
The input trigger is reset through cancelation of the commands "Motor CCW" or
"Disable quick stop" (in the process image). This applies only in the case of control via
manual local mode or in the case of a retentive Quick Stop signal.
Note
No quick stop CW in the case of direct-on-line starters
You cannot use quick stop CCW in combination with direct-on-line starters.