Product features
5.7 Device versions
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
47
5.7
Device versions
Current ranges
The table below shows the switchable motor powers depending on the primary voltage,
according to DIN EN 60947-4-1: Table G.1. The stated current ranges are valid for the
ET 200SP motor starters.
0.1 … 0.4 A
0.3 … 1 A
0.9 … 3 A
2.8 … 9 A
4 ... 12 A
0.1 A
0.4 A
0.3 A
1 A
0.9 A
3 A
2.8 A
9 A
4 A
12 A
230 V AC
< 0.06 kW 0.09 kW < 0.06 kW 0.18 kW 0.18 kW 0.55 kW 0.55 kW 2.20 kW 0.75 kW 3.0 kW
400 V AC
< 0.06 kW 0.12 kW < 0.09 kW 0.25 kW 0.37 kW 1.10 kW 1.50 kW 4.00 kW 1.5 kW 5.5 kW
500 V AC
< 0.06 kW 0.18 kW < 0.12 kW 0.37 kW 0.55 kW 1.50 kW 1.50 kW 4.00 kW 2.2 kW 5.5 kW
The assignments of the motor currents to the motor powers are recommended values. Due
to the introduction of energy-efficient motors (IE3, IE4) to the market, rated currents are
falling for any given power. At the same time, the start-up currents rise.
NOTICE
Dimensioning instructions
Take the current characteristics of the connected motor and motor starter into account
when dimensioning. The following characteristic values are relevant:
•
Ratio of rated current to motor starting current
•
The maximum starting current of the motor may deviate from the values specified by the
manufacturer by 20% in accordance with EN 60034-1.
•
Maximum permissible current range of the motor starter: The permissible current range
can be found in the graphic in Chapter "Device protection model (Page 95)".
You will find more information on dimensioning switching devices for IE3/IE4 motors in the
Switching devices application manual
http://support.automation.siemens.com/WW/view/en/94770820