Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
42
Manual, 07/2016, NEB926157502000/RS-AB/003
3.6.2.8
Technical data 3TK2820
3TK2820-.AJ..
3TK2820-.AL..
3TK2820-.CB..
EMC emitted interference
IEC 60947-5-1, IEC 61000
Item designation
•
according to DIN 40719 extendable after
IEC 204-2 according to IEC 750
—
•
according to DIN EN 61346-2
F
Number of sensor inputs 1-channel or
2-channel
1
Design of the cascading
—
Type of the safety-related wiring of the inputs
single-channel and two-channel
Product feature transverse contact-secure
Yes
Safety Integrity Level (SIL) according to
IEC 61508
SIL3
SIL claim limit (for a subsystem) according to
EN 62061
3
Safety integrity level (SIL) for delayed release
circuit according to IEC 61508
—
Performance Level (PL)
•
according to ISO 13849-1
e
•
for delayed release circuit according to
ISO 13849-1
—
Category
•
according to EN 954-1
—
•
according to ISO 13849-1
4
Safety device type according to IEC 61508-2
Type A
Probability of dangerous failure per hour
(PFHD) with high demand rate according to
EN 62061
1/h 0.00000000094
T1 value for proof test interval or service life
according to IEC 61508
a 20
Number of outputs as contact-affected
switching element as NO contact safety-related
•
as NC contact for reporting function
instantaneous switching
1
•
as NO contact safety-related instantaneous
switching
3
•
as NO contact safety-related delayed
switching
0