Description of the individual safety relays
3.8 3TK28 safety relays with contactor relay enabling circuits
3TK28 safety relays
Manual, 07/2016, NEB926157502000/RS-AB/003
163
3.8.3.7
Technical data 3TK2853
3TK2853-2B...
3TK2853-1B...
EMC emitted interference
IEC 60947-5-1, IEC 60000-4-3,
IEC 60000-4-5, IEC 60000-4-6
Item designation
•
according to DIN 40719 extendable after IEC 204-2
according to IEC 750
KT
•
according to DIN EN 61346-2
F
Number of sensor inputs 1-channel or 2-channel
1
Design of the cascading
cascading and in-service switching
Type of the safety-related wiring of the inputs
single-channel and two-channel
Product feature transverse contact-secure
Yes
Safety Integrity Level (SIL) according to IEC 61508
SIL3
SIL claim limit (for a subsystem) according to EN 62061
3
Safety integrity level (SIL) for delayed release circuit
according to IEC 61508
—
Performance Level (PL)
•
according to ISO 13849-1
e
•
for delayed release circuit according to ISO 13849-1
—
Category
•
according to EN 954-1
4
•
according to ISO 13849-1
4
Safety device type according to IEC 61508-2
Type B
Probability of dangerous failure per hour (PFHD) with high
demand rate according to EN 62061
1/h 0.000000011
T1 value for proof test interval or service life according
to IEC 61508
a 20