Connection
5.4 Plugging in terminal blocks
3TK28 safety relays
194
Manual, 07/2016, NEB926157502000/RS-AB/003
5.4
Plugging in terminal blocks
WARNING
Hazardous voltage
Can Cause Death, Serious Injury, or Property Damage.
Before starting work, therefore, disconnect the system and devices from the power supply.
Requirements
You must have removed the terminal blocks, for the purpose of replacing a device, for
example.
Procedure when plugging in the terminal blocks
Note
Removable terminal blocks are mechanically coded to prevent polarity reversal
The removable terminal blocks are mechanically coded to prevent polarity reversal and are
labeled with A, B, C or D on the inside. Only use the slots shown in the diagram below.
Note
Plug-in sequence
Connect terminal block B before terminal block A, and D before C.
Note
The procedure is shown applied to the 45 mm housing. The procedure for 22.5 mm devices
is analogous.
Step
Operating instruction
Figure
1
Insert the removable terminal block into the
mechanically coded guiderail of the device
①
.
2
Slide the removable terminal block back until it
audibly engages.
3
Check that the clip of the removable terminal
block closes flush with the front panel
②
.