Description
2.5 Standards and guidelines
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
67
Safety clearances between molded case circuit breakers
No minimum clearance needs to be observed between the molded case circuit breakers on
the longitudinal sides (see table above).
The following safety clearances apply to molded case circuit breakers installed directly on
top of each other:
x
See tables below for minimum clearance
①
Front connection with cable, direct
②
Front connection with cable lug
③
Front connection with flat busbar
④
Rear connection with plug-in base or busbar terminals
⑤
Insulation of cable
⑥
Insulation of busbar
Minimum clearance for 3VA1 molded case circuit breakers:
Minimum clearance for 3VA2 molded case circuit breakers: