Applications
3.2 Use of the 3VA1 breaker as a switch disconnector
3VA molded case circuit breakers
126
Manual, 04/2015, A5E03603177010-02
3.2
Use of the 3VA1 breaker as a switch disconnector
Switch disconnectors are deployed as:
●
Disconnectors in subdistribution and final distribution boards
●
Bus couplers
●
Disconnectors for machine line-ups, e.g. as maintenance or repair breakers
●
Operator controls and disconnectors for cables, busbars and device line-ups
●
Application as mains supply disconnectors
●
Application as main switches
●
Isolation of small distribution systems in industrial/commercial buildings
●
Disconnection of loads
Switch disconnectors are capable of switching equipment and parts of electrical installations
when they are conducting their operational current under normal operating conditions.
Switch disconnectors do not have an overload or short-circuit release. For this reason, a
molded case circuit breaker or a fuse must be installed upstream of every switch
disconnector. Refer to chapter Upstream protection of switch disconnectors (Page 130).
Compatibility of 3VA switch disconnectors and accessories
3VA1 switch disconnectors have been developed from the 3VA1 molded case circuit breaker
design. Both share the same attributes listed below:
●
Sizes
●
Dimensions
●
Mounting options
●
Procedure for installing accessories
This means that a shunt trip can trip the switch disconnectors by remote control, or that the
disconnector can be opened or closed by a side wall mounted rotary operator.
Summary of Contents for 3VA1 100 A
Page 1: ......
Page 2: ......
Page 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Page 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Page 532: ......