Communication System Manual
3WN1, 3WS1 Circuit-Breakers
104
Copyright Siemens AG 1998. All rights reserved.
Version 1.0 (08/98)
The interface module has been tested in accordance with the tests, standards and specifications outlined in
the following table.
Table 15 Tests, standards and specifications
No.
Parameter
Data
Description
1
Vibration test
•
5 Hz
≤
f
≤
26 Hz, amplitude =
0.75 mm
•
26 Hz
≤
f
≤
500 Hz, acceleration =
20 m/s
2
à
Frequency sweep: 1 octave/min
à
10 freq. sweeps each in x, y, z
ð
SN 31205
(IEC 68-2-6-Fc sinusoidal)
(= utilization category: 3M6/1M4)
2
Shock test
•
Shock form = half sinusoidal
•
Acceleration = 15 g (150 m/s
2
)
•
Duration of shock = 11 ms
à
3 shocks in +/- direction in x, y, z
ð
SN 31205 (IEC 68-2-27-Ea)
(= utilization category: 3M6/1M4)
3
Drop test
1m high
ð
SN 18013
4
Bending and draw-out test
•
Screw size: M3
--> tightening torque: 0.5 ... 0.8 Nm
•
Wire
cross-section: 0.75/1.5/2.5 mm
2
AWG: 18/16/14
•
Wire type : rigid, flexible
ð
IEC 947-1 (screw connections)
5
Climatic test:
- Cold
- Dry heat
- Change of temp.
- Damp heat
•
0
°
C/16 h
•
60
°
C/16 h
•
-25
°
C ... 55
°
C, 1
°
C/min, 2 cycles
•
55
°
C, 90 ... 95 %, 12+12h, 2 cycles
ð
SN 31205 (IEC 68-2- 1-Ad,
IEC 68-2- 2-Bd,
IEC 68-2-14-Nb,
IEC 68-2-30-Db)
(= utilization category: 3K6/1K6)
6
Pollutant concentration
•
SO2 < 0.5 ppm; rel. humidity < 60 %
•
H2S < 0.1 ppm; rel. humidity < 60 %
ð
SN 31205 (IEC 68-2-60)
(= utilization category: 3C3/1C2)
ð
No condensation
7
ESD
8 kV discharge in air
6 kV contact discharge
IEC 1000-4-2 Severity 3
8
Electromagnetic fields
10 V/m
IEC 1000-4-3 Severity 3
9
Burst
2 kV/5 kHz supply voltage
2 kV/5 kHz data cables
IEC 1000-4-4 Severity 3
10
Emitted interference
Limit class A
EN 55011
11
Approvals
•
UL
•
CSA
•
CE mark
•
PROFIBUS certification
ð
Underwriters Laboratories
ð
Canadian Standards
Association
ð
Certificate of conformity from
ð
PROFIBUS user organization
12
Standards, specifications
•
DIN 40050; IEC 529
•
VDE 0106, protection class 3
•
VDE 0160, where applicable
•
VDE 0110 - insulator group IIIa, IIIb
- pollution severity 3
•
IEC 68
•
IEC 721-3-1/-3
•
IEC 1131-2
•
IEC 1000-4-2/-3/ -4/ -5/ -6
•
EN 55011, DIN VDE 0875-11
•
EN 50022
•
EN 61131-2
•
UL 508
•
CSA 22.2-14
ð
IP degrees of protection
ð
Shock protection, protective
separation
ð
Power installations
ð
Insulation coordination
ð
Env. conditions: Meas. methods
ð
Env. conditions: Definitions
ð
PLC interface standard
ð
EMC requirements
ð
EMC emissions
ð
Standard DIN rail
ð
PLC I/O modules
ð
UL for indust. control systems
ð
CSA for industrial equipment
13
Siemens standards
•
SN 18013
•
SN 18012
•
SN 36350
•
SN 31205
ð
Packaging and drop test
ð
Labeling of packaged items
ð
Recycling guidelines
ð
Environmental conditions