Communication System Manual
3WN6 Circuit-Breakers
Version 1.0 (05/98)
Copyright Siemens AG 1998. All rights reserved.
39
3.4.2 List of acyclic 3WN6 messages on PROFIBUS-DP
x =
1
Test unit + delivery
date
500, 1, 0, 0, 0
1 - 111194
-
-
2
Identifier number
500, 2, 0, 0, 0
0 - 99
-
-
4
Rated current of
circuit-breaker
500, 4, 0, 22, 0
315 - 3200 A
315 - 3200 A
315 - 3200 A
5
Function test of
release
500, 5, 0, 0, 0
0 - 3
19)
0 - 3
19)
0 - 3
19)
11
Circuit-breaker size
502, 1, 0, 0, 0
1 - 2
-
-
12
Circuit-breaker
type
502, 2, 0, 0, 0
2
-
-
13
No. of poles
502, 3, 0, 0, 0
3 - 4
-
-
14
Version of release
unit (in ASCII
code)
502, 4, 0, 0, 0
"N" or "P"
(ASCII code)
"H" or "J"
(ASCII code)
"D" or "E"
(ASCII code)
15
Revision level of
communication
502, 5, 0, 0, 0
(2 bytes:
ha
software)
(2 bytes:
ha
software)
(2 bytes:
ha software)
16
Communication
module version
502, 6, 0, 0, 0
11; 91
20)
11
20)
11
20)
17
Revision level of
release unit
502, 7, 0, 0, 0
(2 bytes:
ha
software)
(2 bytes:
ha
software)
(2 bytes:
ha software)
21
Communication
address
503, 1, 0, 0, 0
21)
21)
21)
17)
The message addresses are shown as decimal numbers in the following; input must be in binary format.
18)
The value ranges shown here and on the following pages are transferred in the corresponding binary format.
19)
0: System 0K; 1: Bus error; 2: CT recognition module error; 3: LCD error.
20)
11: Communication functions (Z=F01 in order number); 91: Communication and measurement functions (Z=F05)
21)
Not supported at present.
Message group 0
M.
no.
Designation
Message
address
17)
Value range
18)
Value range
18)
Value range
18)
0:x
Circuit-breaker
key data
Releases
N and P
Releases
H and J/K
Releases
D and E/F
Note: Circuit-breaker key data, i.e. messages 0:1 to 0:21 are "read only" data.