Communication System Manual
3WN6 Circuit-Breakers
Copyright Siemens AG 1998. All rights reserved.
Version1.0 (05/98)
50
T-Nr. RELEASE
N and P
H and J/K
D and E/F
Message address
1:111 Additional functions 1
812, 1, 0, (OS1), 0, 0, 0
Note: Message address 812, 1, 0 is sufficient for reading.
OS1:7
OS1:6
OS1:5
OS1:4
OS1:3
45)
Optional trip (1) or alarm
(0)
OS1:2
X
Only with communication module with measurement
functions (Z=F05)
Reserved
OS1:1
46)
Earth fault trip (1) or
alarm (0)
OS1:0
X
X
X
OS 1:0 for releases E/F, J/K and P only
OS2:7
OS2:6
OS2:5
OS2:4
OS2:3
OS2:2
OS2:1
OS2:0
OS3:7
OS3:6
OS3:5
OS3:4
OS3:3
OS3:2
OS3:1
OS3:0
45)
If bit OS1:2 is set (= optional trip), the "fault signals" (parameter identifier 748, 1 ,0) is registered in "group fault signal’ of the main status word and a trip
is therefore generated for all "fault signals". If bit OS1:2 = 0 (= alarm), "fault signals" do not generate a trip, they are merely registered in the "group
warning signal" of the main status word. "Fault signals" can also be individually deactivated (by setting message numbers 1:101 to 1:106 to 0).
46)
If bit OS1:0 is set, an earth fault is registered in the "group fault signal" and a circuit-breaker trip is generated if an earth fault occurs. If bit OS1:0 = 0 (=
alarm), the occurrence of an earth fault is registered in the "group warning signal" of the main status word, and no trip is generated in this case.