Siemens IK PI · 2004
6/14
AS-Interface
AS-Interface safe compact modules
AS-Interface Safety at work
6
■
Schematics
Logical assignments
K45F Safe Compact Module
If only one single-channel switch will be connected to the mod-
ule, this must be connected to Channel 1. The second channel
must be bridged. This can be performed with the M12 connector
3RK1901-1AA00 on Socket 2.
Pin 3 of Socket 1 is connected to Pin 1 of Socket 2 and Pin 4 of
Socket 1 is connected to Pin 2 of Socket 2. If both socket pairs
are assigned, the inputs are linked.
K60F
Safe Compact Module
Pin 3 of Socket 1 is connected to Pin 1 of Socket 2 and Pin 4 of
Socket 1 is connected to Pin 2 of Socket 2. If both socket pairs
are assigned, the inputs are linked.
Socket
Assignment / data sheet / function
1
Pin 1 and Pin 2: affects bits D0 and D1 = Channel 1
Pin 3 and Pin 4: affects bits D2 and D3 = Channel 2
Pin 5 not assigned
2
Pin 1 and Pin 2: affects bits D2 and D3 = Channel 2
Pin 5 not assigned
3
Unused
4
Unused
²
1
2
3
4
ADDR
1
2
3
4
G_NSA0_XX_00355
Socket
Assignment / data sheet / function
1
Pin1 and Pin 2: affects bits D0 and D1 = Channel 1
Pin 3 and Pin 4: affects bits D2 and D3 = Channel 2
Pin 5: unused
2
Pin 1 and Pin 2: affects bits D2 and D3 = Channel 2
Pin 5: unused
3/4/7 and
8
Not assigned, factory sealed
5
Pin 4: Output 1
Pin 3: --
Pin 5: Ground
Pin 1 and Pin 2: unused
6
Pin 4: Output 2
Pin 3: --
Pin 5: Ground
Pin 1 and Pin 2: unused
3
4
2
N S A _ 0 0 3 5 8
1
3
7
5
1
4
8
6
2