Siemens IK PI · 2004
6/36
AS-Interface Master
CP 243-2
Masters for SIMATIC S7
6
■
Technical specifications
■
Ordering data
Order No.
AS-Interface Specification
V 2.1
Interfaces
• Address space used in the PLC
Corresponding to 2 I/O modules
(8 DI/8 DO and 8 AI/8 AO)
• AS-Interface connection
Terminal
Current consumption
• Via AS-Interface
Max. 100 mA
• Through backplane bus
Typ. 220 mA at 5 V DC
Power loss
Approx. 2 W
Perm. environmental conditions
• Operating temperature
- Horizontal mounting
0°C to +55°C
- Vertical mounting
0°C to +45°C
• Transport/storage temperature
-40 °C to +70 °C
• Relative humidity
Max. 95% at +25 °C
Design
• Module format
S7-22x expansion module
• Dimensions (W x H x D) in mm
71.2 x 80 x 62 (H+16 mm with
holes for wall mounting)
• Weight
Approx. 250 g
• Space required
1 slot
CP 243-2
communications processor
6GK7 243-2AX01-0XA0
For connection of SIMATIC S7-200
(2
nd
generation) to AS-Interface
with bus connector
Manual for CP 243-2
Including AS-Interface
fundamentals and diskette
with program examples
paper version
• German
6GK7 243-2AX00-8AA0
• English
6GK7 243-2AX00-8BA0
• French
6GK7 243-2AX00-8CA0
• Spanish
6GK7 243-2AX00-8DA0
• Italian
6GK7 243-2AX00-8EA0