background image

 

 

Installation Instructions

Document No. 563-067

February 23, 2011 

 

Room Sensor Transceiver (RSX)

 

 

Item Number 563-067, Rev. BA

 

Page 1 of 5

 

 

Figure 1.  Room Sensor Transceiver. 

Product Description 

The Room Sensor Transceiver (RSX) allows 
wireless communication between the Terminal 
Equipment Controller (TEC) and Wireless Room 
Sensor (WRS). The RSX is mounted at or near the 
TEC and is powered by 24 Vac. The RSX is 
connected to the TEC using the RSX/TEC 
connection cable. The antenna can be mounted 
directly to the radio or mounted remotely for 
installations where the location of the RSX causes 
the antenna to be shielded—for example, when the 
RSX is mounted inside a TEC enclosure. 

Product Numbers 

563-069 

Room Sensor Transceiver (RSX)  

563-007 

Direct Mount Antenna 

563-008 

Remote Mount Antenna 
 

 

Transceivers do not come with antennas. 
Antennas must be ordered separately. 

 

Accessories 

563-210-01 

RSX/TEC Connection Cable (3 ft) 

563-210-02 

RSX/TEC Connection Cable (12 ft) 

563-207 

Auto-binding cable (to bind 
WRS/RSX pair) 

Warning/Caution Notations 

CAUTION: 

 

Equipment damage or loss of 
data may occur if you do not 
follow the procedures as 
specified. 

 

Expected Installation Time 

10 minutes 

Required Tools and Materials 

 

Electro-static discharge wrist strap 

 

Small flat-blade screwdriver 

 Cordless 

drill/driver 

set 

Prerequisites 

 

All wiring must conform to NEC and local 
codes and regulations. 

 

24 Vac Class II power source is available 
with enough power to support RSX (RSX 
draws 1.2 VA). 

 

Metal Oxide Varistors (MOVs) must be used 
for TECs that switch high voltage devices. 
For details, see the FSN for 

Terminal 

Equipment Controllers (TECs) Failing when 
Switching High Voltage Powered Devices

 

Any application-specific hardware or device 
is installed. 

Summary of Contents for 563-069

Page 1: ...8 Remote Mount Antenna Transceivers do not come with antennas Antennas must be ordered separately Accessories 563 210 01 RSX TEC Connection Cable 3 ft 563 210 02 RSX TEC Connection Cable 12 ft 563 207 Auto binding cable to bind WRS RSX pair Warning Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Expected Installation Time 10 min...

Page 2: ...ng plenum with the entire antenna extending downwards below the VAV box Figure 2 Remote Mount Antenna The RSX is mounted inside the TEC or any metal enclosure and the antenna is brought through a 1 2 in 1 3 cm knockout Figure 3 The antenna extension cable is 12 in 30 cm long WLAN0088R1 VAV BOX VAV BOX VAV BOX Figure 2 RSX Mounted Outside Enclosure WLAN0089R1 Figure 3 RSX Mounted Inside Enclosure N...

Page 3: ...ce as shown b Connect E on the RSX power connector to earth ground as shown 24 V AC C E H C H DO 1 DO 2 DO 3 DO 4 DO 5 NO C NO C NO C NO C NO C DO 6 DI 3 DI 2 FLN TRUNK NO C AI 3 TX RX S BST RTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 WLAN0090R1 TEC Power From Transformer TEC Typical Ground 24 Vac Power Line Alternate Power 3MTM ScotchlokTM Power Connectors Ty...

Page 4: ...ed Page 4 of 5 Siemens Industry Inc c Connect the antenna wire securely to the RSX 6 Position the antenna in a vertical orientation up or down 7 Install and bind associated Wireless Room Sensor WRS to the RSX If the associated WRS is new or is shipped with the RSX install WRS per the Wireless Room Sensor WRS Installation Procedure 563 065 If the associated WRS is already installed bind the RSX and...

Page 5: ...nce will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equi...

Reviews: