background image

 

GAMMA 

instabus

 

Technical product information 

June 2010 

Switching actuator, main module N 513/11 

5WG1 513-1AB11 

3x AC 230/400V, 20AX, C-load, load-check  

 

Siemens AG 

N 513/11, 6 pages 

Technical manual 

Industry Sector, Building Technologies 

Low Voltage Distribution 

© Siemens AG 2010 

Update: http://www.siemens.com/gamma 

P.O. Box 10 09 53, D-93009 Regensburg 

Subject to change without further notice 

 

 

2.4.3.6/1 

Product and functional description 

 

 

 

The switching actuator main module N 513/11 is a DIN-

rail mounted device in N-system dimensions. It can 

switch three groups of electrical consumers, independent 

of each other, via its three relay contact outputs, each 

with load current measurement and monitoring (load-

check). The bus is connected via a bus terminal block. 

The actuator electronics are supplied via the bus voltage. 

 

Connection of switching actuator sub-modules 

A switching actuator sub-module N 513/21, N 512/21 or 

N 562/21 (see device B in figure 1) can be connected to 

the switching actuator main module N 513/11 (see de-

vice A in figure 1) via the 6-pin interface with a special 

jumper. A further switching actuator sub-module can be 

connected likewise to a previous switching actuator sub-

module. In total up to 4 switching actuator sub-modules 

N 513/21, N 512/21 or N 562/21 can be connected in 

series to a switching actuator main module N 513/11, so 

that a main module, if need be, can be extended simply 

from a 3-fold to a 6-, 9-, 12- or 15-fold switching actua-

tor and thus be matched flexibly to the size and number 

of loads to be switched. 

 

LED display 

Five green light emitting diodes (LED) on the top of the 
main module (see figure 2, A5) indicate which module is 
selected (LED = ON). A module can be selected by tap-
ping the pushbutton “Direct mode” (see figure 2, A6) 
once or several times until the LED of the desired module 
A to E illuminates. If any of the green LED A to E is flash-
ing a fault was detected at this module. For example, this 
is the case if more modules are configured than are actu-
ally connected or if the configured module type does not 

correspond with the module type actually connected or if 
a module is detected as faulty.  

 

Bus mode / direct mode 

The direct mode pushbutton (see figure 2, A6) with an 

integrated yellow LED may be used to toggle between 

bus mode and direct mode. If this pushbutton is pressed 

briefly, the associated green LED indicates for 30 seconds 

which of the modules A to E (see figure 2, A5) was se-

lected last and the switching state of the corresponding 

outputs is indicated by the red LED integrated in buttons 

1 to 3 (see figure 2, A9; relay contact closed: LED = ON, 

contact open: LED = OFF).  

However, if the button to switch on direct mode is held 

down for at least 3 seconds, then the yellow LED to indi-

cate direct mode turns on permanently. In direct mode, 

each output of the currently selected module can be 

switched via the allocated pushbutton on the top of the 

main module through a toggling function: a first press on 

the pushbutton switches the output on if it is switched 

off, a second press switches it off again. The switching 

state of the output is indicated by the red LED incorpo-

rated in the pushbutton. (Note: Pushbuttons 4 to 6 and 

the incorporated LED are not used in the N 513/11.)  

To change the switching state of the outputs of another 

module, this module must be selected first. To do this, 

you must briefly press the direct mode pushbutton sev-

eral times until the LED of the desired module A to E 

illuminates. Modules that are connected but not yet set 

up as connected cannot be selected.  

A parameter determines whether direct mode can be 
switched on permanently or for a limited period. The 
factory default setting limits the direct mode period to 15 
minutes. Each time the pushbutton is pressed the timer 
is reset to 15 minutes. After the period has elapsed with-
out a further key press, direct mode is switched off 
automatically and bus mode is re-enabled accordingly (if 
communication via the bus is possible). Alternatively, 
direct mode can be left at any time by pressing the direct 
mode pushbutton for at least 3 seconds. Then the yellow 
LED for indicating direct mode turns off and the actuator 
operates in bus mode. In bus mode, pressing the 
pushbutton for direct switching of an output off or on 
does not work. If direct mode is active, switching and 
scene recall commands received via the bus are buffered 
and automatically executed after switching back to bus 
mode. 
 

Behavior in case of mains failure / recovery 

Because the actuator electronics are fed from the bus, a 
mains failure then leads solely to a failure of the actuator 
function if the bus voltage also fails as the result of a 
mains failure. However, it can be set for each actuator 

Summary of Contents for 5WG1 513-1AB11

Page 1: ...o toggle between bus mode and direct mode If this pushbutton is pressed briefly the associated green LED indicates for 30 seconds which of the modules A to E see figure 2 A5 was se lected last and the switching state of the corresponding outputs is indicated by the red LED integrated in buttons 1 to 3 see figure 2 A9 relay contact closed LED ON contact open LED OFF However if the button to switch ...

Page 2: ...itoring of the load current for each output on load failure and or overload simultane ous switching of all 3 outputs 3 phase switching con version of a speed given as a percentage value into 1 to 3 stage switching commands fan speed control con version of a valve setting given as a percentage value into a pulse width modulated PWM switching com mand thermal drive control a switching cycle and oper...

Page 3: ...9 outputs 5 with 12 outputs 4 with 15 outputs Operating elements 1 commissioning push button for toggling between normal mode addressing mode 1 push button for toggling between bus mode direct mode 6 push buttons for direct operation toggling of up to 6 actuator out puts independent of the bus Display elements 1 red LED for checking the bus voltage and for display ing normal mode addressing mode 5...

Page 4: ... Jack for connection of a switching actuator sub module A5 LED to indicate the selected device A6 Pushbutton to toggle between Bus and Direct mode A7 LED to indicate Direct mode On A8 Pushbutton for direct operation of outputs 1 3 A9 LED to indicate whether the corresponding output is switched on or off A10 Without function A11 Without function A12 Screw type terminals of outputs 1 3 Installation ...

Page 5: ... further notice 2 4 3 6 5 Dimension drawing Dimensions in mm b 90 44 55 45 b 3 module units 1 module unit MU 18 mm General notes The operating instructions must be handed over to the client A faulty device shall be sent with a Return Good Note for Service provided by the appropriate Siemens sales office to the following address SIEMENS AG Siemensstr 10 D 93055 Regensburg If you have further questi...

Page 6: ... 1AB11 3x AC 230 400V 20AX C load load check Technical manual N 513 11 6 pages Siemens AG Industry Sector Building Technologies Update http www siemens com gamma Siemens AG 2010 Low Voltage Distribution Subject to change without further notice P O Box 10 09 53 D 93009 Regensburg 2 4 3 6 6 Space for notes ...

Reviews: