GAMMA instabus
Technical Product Information
June 2022
IP Gateway KNX/BACnet N143
5WG1143-1AB01
6 / 12
Siemens Schweiz AG
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH 6300 Zug
A6V10466141 RS-AC
Siemens AG 2022
Subject to change
Update
http://www.siemens.com/gamma-td
Beneath the header is a table listing all configured objects. The table is divided into the following columns:
Object number
Object name
BACnet object ID
KNX group address
Datapoint type
Transmission mode
Reading during initialisation
Unit
Object value
Object values are not dynamically up-dated on the website. To up-date the objects, please re-load the website.
The revision number increases on every download on ETS.
An EDE (Engineering Data Exchange) list can be exported as csv file format via the button „Export EDE“ on the
right side of the web page.
Note
In general, the webpage is coded for the UTF-8 character set. A selection field on the web page allows switching
between UTF-8 and ISO 8859-1 encoding.
When ETS is used for configuration then texts (including special characters) are coded dependent on the set-
tings in ETS. The encoding is set in ETS for the project under General - Codepage. The UTF-8 character set should
be selected. Texts to be communicated via BACnet are transmitted as entered in ETS.
Integrated KNXnet/IP interface
The device also has a KNXnet/IP interface to enable a connection to the ETS for remote parameterization. This
interface can be deactivated via an ETS parameter.
Hint
The KNXnet/IP interface is deactivated in the ETS parameters for security reasons. To use it, it must first be
activated by a corresponding ETS parameter under "Options".