SD62 

OPERATION 

 
With the air supply on, turn the needle valve to obtain the desired flow rate. The best rate will depend on the volume 
of air in the system and the desired speed of response to level changes. Ordinarily, a rate of 0.9 SCFH (minimum 
flow for Model 62V) is considered satisfactory, although this may have to be increased to obtain the desired speed 
of response, particularly if the system contains much volume or is subject to rapid pressure or level fluctuations. The 
flow rate should be checked to make sure it is not excessive, by noting that the receiving meter does not change by 
an objectionable amount when the flow rate is doubled. 
 
The Model 62V relay may be used with or without a flow indicator in the downstream line. This is possible since the 
needle valve in the Model 62V has an internal bypass which permits a minimum flow of 0.9 SCFH even with the 
adjusting screw seated. This prevents possible damage to the process by eliminating the chance of shutting down the 
operation of the system by turning the screw in. 
 
The Model 62VN differs from the Model 62V in that the internal bypass has been eliminated. This permits flows of 
less than 0.9 SCFH. It is recommended that a flow indicator be used in the downstream line since it is possible to 
shut this unit off completely. 
 

MAINTENANCE 

 
The use of a Constant Differential Relay greatly reduces the maintenance ordinarily required with the conventional 
purging or bubbling system. The rate of flow of the purging gas can be expected to remain constant over long 
periods of time. Any change in this rate is probably caused by partial clogging of the needle valve and can easily be 
corrected by screwing the valve in, then resetting to the desired flow rate. In case of severe clogging, due to the 
presence of excessive dirt in the air supply line, it may be necessary to remove the needle valve for a thorough 
cleaning. 
 
No lubrication of any sort is required for the constant differential relay. 
 
When disassembling the unit, make sure all parts are clean and free of dirt and debris. Reassembly is the reverse 
order of disassembly. Make sure not to damage the O-ring(s) and diaphragm(s) when reassembling the unit.  

 
Parts Replacement 

 
Refer to the Parts List at the back of this instruction when performing maintenance. It provides a list of replacement 
parts and a schematic of the instrument. 
 

CAUTION 

Before disassembling the instrument, turn off supply air pressure to the instrument. 

 

 

5

Summary of Contents for 62 Series

Page 1: ...s diaphragm controls the action of a valve plunger to automatically admit supply air to the needle valve at the required rate A self contained automatic bleed discharges excess supply air to the atmosphere when necessary The constant differential relay is made of aluminum brass stainless steel Neoprene and Buna N The rotameter is constructed of aluminum stainless steel borosilicate glass Buna N O ...

Page 2: ...e kept as short as possible and should be at least 1 4 pipe or larger For example At a flow rate of 0 9 SCFH the pressure drop in a 20 foot length of 1 4 pipe will not exceed 0 20 H20 head but approximately ten times this drop would be obtained with 1 4 O D tubing Pressure drop between the relay and the junction of the receiving instrument is ordinarily of no consequence so that this line may be m...

Page 3: ...SD62 Figure 1 Installation Dimensions with Rounded Rotameter 3 ...

Page 4: ...e instrument should be no larger than 3 microns Dew Point The dew point at line pressure should be at least 10 C 18 F below the minimum temperature to which any part of the instrument air system is exposed at any season of the year Under no circumstances should the dew point at line pressure exceed 2 C 35 6 F Oil Content Maximum total oil or hydrocarbon content exclusive of non condensable should ...

Page 5: ...nated This permits flows of less than 0 9 SCFH It is recommended that a flow indicator be used in the downstream line since it is possible to shut this unit off completely MAINTENANCE The use of a Constant Differential Relay greatly reduces the maintenance ordinarily required with the conventional purging or bubbling system The rate of flow of the purging gas can be expected to remain constant ove...

Page 6: ...elect the product line e g Control Solutions Warranty The sales contract contains the entire obligation of Siemens The warranty contained in the contract between the parties is the sole warranty of Siemens Any statements continued herein do not create new warranties or modify the existing warranty All product designations may be trademarks or product names of Siemens Industry Inc or other supplier...

Page 7: ...ly 1 12 1145 19 Mounting Bracket 1 13 7135 19 Diaphragm 1 14 8912 10 Retaining Screw Model 62VN only 1 15 2155 225 Filter Screen 2 A6X30060272 Rotameter Rounded Not shown A Models only Supersedes the following part 1 12431 11 Rotameter Rectangular Not shown A Models only Discontinued part A 1 3345 1 4 20 x 7 8 Lg Fil HD Screw 3 B 1 3410 1 4 20 x 1 Lg Fil Hd Screw 3 C 1 7303 1 4 Med Lockwasher 6 Re...

Reviews: