2.4 Generator Connectivity
The UPS solution offers the possibility of connecting up an external diesel generator
through a specially designed supporting product, the Generator Connect Feeder Pillar.
This adaptation of the normal large feeder pillar allows a portable generator to be used as
a substitute for the mains supply in cases of extended power outages.
See section 12.6 for more information on the Generator Connect Feeder Pillar.
2.5 Electrical Information
Parameter
Value
Input:
Voltage
230Vac (150Vac – 328Vac without switching to battery support)
Frequency
50Hz / 60Hz Auto-detect (±5%)
Current (at max battery
charging current)
FXM1100: 8A at 230Vac
FXM2000: 15A at 230Vac
Mains Input Circuit Breaker
Rating
20A at 230Vac
Output:
Voltage
230Vac
Frequency
50Hz / 60Hz Auto-detect (±5%)
Maximum Power
FXM1100: 1100 W/VA
FXM2000: 2000 W/VA
Waveform
Pure Sine Wave
Switching Time
<5ms
Voltage Distortion
<3% THD
Efficiency
Normal mode (LINE): >98%
Battery support mode (INVERTER): >82%
Battery Charging:
Charge Current
10A
Temperature Compensation
-5mV/°C/Cell
Battery Type
12V 55Ah Valve Regulated Lead Crystal
Environment:
Operating Temperature
-25°C to +74°C
Operating Altitude
12000ft
Operating Humidity
Up to 95%
Table 2-2: UPS Solution Electrical Information
1
Power output de-rates in high ambient temperatures. See sections 4.1 and 12.5 for details.