Document
Name
UPS Solution General Handbook
Doc. No.
667/HB/47750/000
Copyright
Siemens plc 2017 All Rights Reserved
For Siemens type controllers, please use the Master Switch Panel 300mA RCD Kit –
667/1/27117/000.
A TT Earth Electrode test should be carried out as part of UPS commissioning. See
section 11.2.
7.3 UPS Fault / Alarm Relay Contacts
A total of 18 relay contact termination points are made available via the UPS Connection
Panel (Normally Closed, Normally Open and Common for six relay outputs). These can
be cabled via ducting into the traffic controller for status and fault monitoring of the UPS
Solution. See sections 9.8 and 12.2.1 for details.
Cable selection for this interconnection is dependent on the number of cores required to
terminate all necessary contacts. Refer to Table 7-1 below.
Part Number
Description
998/4/70468/004
Armoured 1/1.13mm 8core PVC cable
998/4/70468/006
Armoured 1/1.13mm 12core PVC cable
998/4/70468/008
Armoured 1/1.13mm 16core PVC cable
998/4/70468/050
Armoured 1/1.13mm 20core PVC cable
Table 7-1: Alarm Contact Cable Specification
7.4 Ethernet Cable
When the FXM Series UPS unit’s LAN interface feature is to be used, CAT5e cable is to
be ducted into the controller cabinet and connected to an IP enabled Ethernet
connection.
Use the cable specified in Table 7-2 for this connection.
Part Number
Description
998/4/88384/000
Armoured CAT5E cable for duct installation
Table 7-2: Ethernet Cable Specification
See section 8.3 and 12.3.3 for LAN connection details.
7.5 Battery Expansion
Additional battery support from the Battery Expansion Cabinet is to be cabled into the
UPS Cabinet using the following armoured cable.
Part Number
Description
998/4/88346/100
Armoured 10mm
2
3core PVC Mains cable
Table 7-3: Battery Expansion Cable Specification
WARNING:
This cable is to be clearly labelled to prevent confusion with Mains
supply chain cabling. Only two of the three cores available are to be used for
battery termination. The Green/Yellow core is to be used to link the main earth
studs of the UPS and Battery Expansion Cabinets.
See sections 9.8 and 9.9 for installation details.