Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
BH17 7ER
Version
7
Page 29 of 76
Status
ISSUED
Last Editor
Ore Oluwatudimu
TS008468
Date
31/01/2017
Document
Name
UPS Solution General Handbook
Doc. No.
667/HB/47750/000
Copyright
Siemens plc 2017 All Rights Reserved
9.2 Preparing and Installing the Reinforced Stool
Step No.
UPS Cabinet
Battery Expansion Cabinet
Refer to
1
Prepare and install the Reinforced Stool
Section 9.2
WARNING:
Prior to installation of the Reinforced Stool, instruct the Civils
Contractor as to the correct orientation of all cabinet stools, ensuring all
cabinets on site will face the right way.
The reinforced stool is based on a normal controller cabinet stool and the installation
process is much the same.
WARNING:
Although similar, the normal ST800, ST900 or ST950 cabinet stool
must not
be used when installing the UPS Solution as it is not capable of
supporting the total weight of all cabinet elements.
1.
Prepare the Reinforced stool by fitting the CET plate to the upward fold in the top
of the stool using the two bolts and fixings provided.
Figure 9-1: Reinforced Stool and CET plate
2.
Have the stool concreted into place in site in accordance with 667/HE/45950/000.
See Figure 9-2.