12.3 Communicating with the UPS Solution
12.3.1 Three-Button Interface
The Alpha FXM UPS unit includes a simple three-button button interface and LCD display
for basic system interrogation while present on site.
Using the three buttons, CANCEL, SCROLL and SELECT, it is possible to access the
following menus:
Control Menu -
Control, program and adjust a limited number of system
options including forcing the UPS unit into ‘INVERTER’
mode.
System Status Menu -
Measure various inputs, outputs and related system values
including the current battery voltage and estimated support
time available.
Alarm and Fault -
Disabled unless the UPS unit has a fault, these menus
display and fault or alarm flags that are currently active.
Event Status Menu -
Allows the user to scroll through the last 25 items listed in the
UPS unit’s 100-event log.
For details on all the options available within these menus, please refer to the Alpha FXM
UPS Operating Manual – 667/HB/47760/000.
Access to many more system settings can only be achieved through the RS232 or LAN
interfaces as described in sections 12.3.2 and 12.3.3.
12.3.2 RS232 Interface
The Alpha FXM UPS unit’s RS232 interface can be accessed via the female 9-way D-
type connector on the unit itself. Table 12-4 below lists the necessary connection details.
Connection Parameters
Required Setting
Duplex Mode
Half Duplex
Handshaking
Software Handshaking
Baud Rate
2400 bps
Data Format
8-bit Data, No Parity, 1 Stop Bit, No Flow Control
Default Password
1111
Table 12-4: RS232 Interface Connection Information
The RS232 Interface’s main menu screen gives the user access to four main subsections
as well as displaying status and fault / alarm information in the following format.