12.5.2 Battery Charging
The UPS Solution offers temperature compensated battery charging to help keep all
battery packs in optimum condition across its extended operating ambient temperature
range. The battery charging voltage is adjusted by
-5.0mV/°C/cell
.
12.5.3 Battery Support Hold Up Times
Ambient temperature plays a big part in determining how much a battery support hold up
time is available. As temperature decreases, the available capacity of each battery pack
is reduced as battery chemistry becomes increasingly inert. This becomes very apparent
and extremely low ambient temperatures.
APPENDIX A – Estimated Hold Up Times shows battery hold up runtime charts (such as
in section 5) adjusted for ambient cabinet temperatures of +20°C, 0°C and -25°C.
12.6 Generators
12.6.1 The Generator Connect Feeder Pillar
As stated in section 2.4, a diesel generator
must
be connected via the Siemens
Generator Connect Feeder Pillar as shown below.
Figure 12-5: Generator Connect Feeder Pillar
This feeder pillar variant incorporates a lockable cable entry point, a 2P+E
IP44 rated
appliance inlet connector and a 63A double-pole changeover switch for isolation and
source selection.
Detailed information on the Generator Connect Feeder Pillar is available in the Isolators
and Feeder Pillar General Handbook – 667/HB/45040/000.
8
Two Pole and Earth