Figure 13-1: Battery Terminals Connected with the Terminal Linking Bar
5.
Connect the positive ring tag from the housing MCB to the positive terminal of
Battery 4. (brown cable)
6.
Replace the battery retention bar.
After Replacing the Battery Pack:
1.
Plug the 48V Battery Connector back into the FXM Unit
2.
Switch all Breakers on the Battery Shelves (Battery Housing Assemblies) in both
cabinets (UPS and Battery Expansion Cabinets) to the
ON
position
3.
Switch the Battery Breaker on the Front left of the Alpha FXM UPS unit to the
ON
position
Finally check that there are no alarms active on the UPS and that the UPS is in Line
mode.