13.4.3 Replacing an Alpha UATS unit
The UPS Cabinet needs to be Isolated before carrying out any work on the UATS or UPS
connection shelves. Please Isolate the cabinet by following the instructions in Section
13.3
Once the Cabinet is Isolated and the UPS is completely switched off, the following steps
can be followed:
1.
Test the input and output terminals to ensure that the unit is completely isolated
from Mains and UPS
2.
Remove the Covers from both sides of the UATS Shelf
3.
Remove the four cable looms from the UATS, ensuring that you know where they
came from.
4.
Replace the UATS Shelf
5.
Wire the Cable looms into the replacement UATS and replace all of the covers.
6.
Switch the UPS back on and check that it’s working properly.
13.5 Second Line Maintenance
It is recommended that undamaged parts are reused where possible.
All other parts must be sent for repair or disposal. Further details are held in the ‘Global
Service Support Plan (ref. 667/PA/47750/000).
NOTE:
Observe Anti-static Precautions at all times.
Faulty parts being returned must always be sent back in the original packaging if
available or in an approved anti-static packaging, along with a fully completed fault label,