9.9 Terminating External Cables into the DC Connection Panel
Step No.
UPS Cabinet
Battery Expansion Cabinet
Refer to
8
N/A
Terminate External Cables into
the DC Connection Panel
Section 9.9
WARNING:
Ensure all power sources are switched off and safely isolated
before installation commences. All switches and MCBs should be in the OFF or
BYPASS position.
1.
Remove the blanking plate of the DC Housing module to reveal the DC
Connection Panel.
2.
The DIN rail terminal blocks are clearly labelled. Terminate the Battery cable
from the UPS cabinet to the TBs marked ‘UPS DC’.
3.
Replace the blanking plate.
See section 7 for further details on external cable specification details.
9.10 Terminating and Connecting the Ethernet Cable
Step No.
UPS Cabinet
Battery Expansion Cabinet
Refer to
9
Terminate and connect the
Ethernet Cable
N/A
Section 9.10
If the FXM UPS unit’s LAN Interface feature is to be used, follow the instructions below to
properly terminate the Ethernet CAT5e cable.
1.
Terminate the CAT5e cable into RJ45 jacks (531/4/03461/000) as a standard
straight-through Ethernet cable at both ends according the Table 9-2 below.
Pin
Colour
1
White – Orange stripe
2
Orange Solid
3
White – Green stripe
4
Blue solid
5
White – Blue stripe
6
Green solid
7
White – Brown stripe
8
Brown solid
Table 9-2: RJ45 Interface Cable Connection
2.
Plug the RJ45 jack into the Ethernet socket marked ‘LAN’ on the FXM UPS unit.
See section 7.4 for cable specification details.