Technical specifications
8
8.1
Technical specifications
Technical specifications of the DI 16×NAMUR HA
Article number
6DL1131-6TH00-0PH1
General information
Product type designation
DI 16xNAMUR HA
Firmware version
V1.0
• FW update possible
Yes
Usable terminal block
TB type H1, M1 and N0
Color code for module-specific color identifica‐
tion plate
CC01
Product function
• I&M data
Yes; I&M0 to I&M3
Engineering with
• STEP 7 TIA Portal configurable/integrated
from version
V16
• STEP 7 configurable/integrated from version V5.6
• PCS 7 configurable/integrated from version
V9.0
• PROFINET from GSD version/GSD revision
GSDML V2.3
Operating mode
• DI
Yes
Redundancy
• Redundancy capability
Yes; With TB type M1
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption (rated value)
95 mA
Current consumption, max.
115 mA
Encoder supply
Output voltage, min.
8.1 V
Short-circuit protection
Yes
Power
Power available from the backplane bus
74 mW
Power loss
Power loss, typ.
2.4 W
DI 16xNAMUR HA
Equipment Manual, 08/2019, A5E39293880-AD
37
Summary of Contents for 6DL1131-6TH00-0PH1
Page 6: ...Security information DI 16xNAMUR HA 6 Equipment Manual 08 2019 A5E39293880 AD ...
Page 8: ...Preface DI 16xNAMUR HA 8 Equipment Manual 08 2019 A5E39293880 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16xNAMUR HA 10 Equipment Manual 08 2019 A5E39293880 AD ...
Page 30: ...Parameters 6 5 Flutter monitoring DI 16xNAMUR HA 30 Equipment Manual 08 2019 A5E39293880 AD ...