Description
The short-circuit diagnostic can be used with the following encoder settings:
• NAMUR encoder
• NAMUR change-over contact
6.4.4
Diagnostics: wire break
Definition
This diagnostic message is enabled when the module has no power, or insufficient power, for the
measurement at the corresponding configured input.
Description
The wire break diagnostic can be used with the following encoder settings:
• NAMUR encoder
• Point of contact with 10 kΩ
• NAMUR change-over contact
• Change-over contact with 10 kΩ
6.4.5
Diagnostics: change-over contact error
Definition
This diagnostic message is enabled when a change-over contact error occurs.
Change-over contact errors can only be detected in the case of error-free recorded input signals.
Description
The change-over contact error diagnostic can be used with the following encoder settings:
• NAMUR change-over contact
• Change-over contact, unconnected
• Change-over contact with 10 kΩ
Parameters
6.4 Explanation of the module/channel parameters
DI 16xNAMUR HA
22
Equipment Manual, 08/2019, A5E39293880-AD
Summary of Contents for 6DL1131-6TH00-0PH1
Page 6: ...Security information DI 16xNAMUR HA 6 Equipment Manual 08 2019 A5E39293880 AD ...
Page 8: ...Preface DI 16xNAMUR HA 8 Equipment Manual 08 2019 A5E39293880 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16xNAMUR HA 10 Equipment Manual 08 2019 A5E39293880 AD ...
Page 30: ...Parameters 6 5 Flutter monitoring DI 16xNAMUR HA 30 Equipment Manual 08 2019 A5E39293880 AD ...