SITRANS VP300 (6DR63..)
A5E03359515-01, 03/2011
25
4.
Confirm the selection with . The set actuator type is displayed.
The factory setting is "Linear <= 60 mm".
5.
If required, set the tight closing function.
Use or to switch to the menu "1 Quick Start > 1.1 Autom. initialization > 1.1.2 Tight closing > Edit".
6.
Select the tight closing function with or
7.
Confirm the selection with . The set tight closing function is displayed. Factory setting is "Off".
8.
Start the initialization by selecting the "Start" command and then "OK" in the menu "1 Quick Start > 1.1 Autom.
initialization > 1.2.3 Initialize".
The progress bar in the display indicates the initialization progress. Once the initialization process has been successfully
completed, the display will show the √ symbol.
9.
Switch to the measurement view by pressing the button until the display shows the following:
Result
Commissioning of the positioner is complete. The initialization settings are saved. After the initialization the positioner will
function with the new settings.