SITRANS VP300 (6DR63..)
A5E03359515-01, 03/2011
29
Electrical data
Basic device without explosion
protection
Basic device with explosion protection
Ex "ia", "ic", "nA", "tb"
Can only be used for floating contact.
Signal level Low
Floating contact, open
Signal level High
Floating contact, closed
Contact load
< 3 V, < 15 μA
For connecting to circuits with the
following peak values
-
U
o
= 5 V
I
o
= 0.5 mA
P
o
= 2.5 mW
C
o
= 1 μF
L
o
= 1 mH
Digital input DI 3 (terminals 81/82); can be activated with switch
②
for safety shutdown
Input resistance
> 20 kΩ
Switch in "enable" position
●
Signal status "0" = Safety shutdown
0 ... 4.5 V or unwired
●
Signal status "1" = normal control
operation
13 ... 30 V
Switch in "disable" position
●
Normal operation; safety shutdown
inactive
0 ... 30 V or unwired
For connecting to circuits with the
following peak values
-
"ia"/"ic":
U
i
= 30 V
I
i
= 100 mA
P
i
= 1 W
C
i
= 22 nF
L
i
= negligible
"nA"/"tb":
U
n
= 30 V
I
n
= 100 mA
Galvanic isolation
The digital input DI 3 is galvanically isolated from the setpoint input I
w
.
Analog output I
y
(terminals 61/62)when using a position feedback module 6DR6003-6J
Auxiliary voltage U
H
+12 ... +30 V
-
For connecting to circuits with the
following peak values
-
"ia"/"ic":
U
i
= 30 V
I
i
= 100 mA
P
i
= 1 W
C
i
= 24 nF
L
i
= 67 µH
"nA"/"tb"
U
n
= 30 V
I
n
= 100 mA
Test voltage
DC 840 V, 1 s
Ports
●
Electrical
Screw terminals 2.5 AWG 28-12
Cable gland (M20x1.5 or ½-14 NPT) or plug M12
●
Pneumatic
OPOS interface (VDI/VDE 3847)