Siemens AG Österreich
Seite 6 von 6
Bestell-Nr.: C98130-A7524-A1-07-7419
SITOP select / 08.2013
Printed in Austria
English
Saving the set time delay: On pressing the reset button (5) permanently for approx. 8 s in the programming mode after setting the time delay, all LEDs (3) are
red. If the reset button is released then, the diagnosis module stores the set time delay and switches on the outputs sequentially. Now the diagnosis module is
in its normal operating mode again. If the reset button is not pressed within 30 s in the programming mode, the diagnosis module automatically switches back
to the normal operation mode without storing a change of time delay. If the supply voltage fails during programming, there will also be no storage.
!
Note: The outputs of the diagnosis module are disconnected during the programming mode. After manual or automatic leaving of programming mode as
well as resumption of power supply after breakdown, the outputs will be switched on automatically!
Installation instructions
Installation on DIN rail (DIN EN 50022-35x7.5/15). The equipment must be installed vertically with the input terminals at the bottom and the output terminals at
the top, in order to ensure adequate heat dissipation. A clearance of at least 50 mm must be allowed above and below the device.
To snap the unit on to the DIN bar, hang it with its nose (A)
into the bar (C)
and press until the spring (B)
snaps into place (see page 2). If difficulty is
experienced in snapping the unit on to the bar, loosen the spring (B)
slightly as described under "Removing the Power Supply Unit". To remove from the DIN
bar, use a screw driver to loosen the spring (B)
in the direction of the arrow.
The 24 V DC supply voltage (8) must be connected in accordance with the national standards. It is only allowed to be connected to a power supply with "safe
electrical isolation" in accordance with EN 60950.
!
Note: The 0 V connection (7) of the device merely serves to supply the internal electronic circuits. The 0 V of the loads must be supplied directly to the
power supply by means of separate lines.
In Ex - applications must be guaranteed that installation is according to protection class IP 54.
Connections and terminal assignment
Terminals Function
Clamping
range
Remarks
Input +24 V
+24 V input voltage connection (from "+"
output of the power supply)
0.33 to 10 mm
2
Screw terminals; use a screwdriver with 5 mm blade width; recommended
tightening torque 1.2 Nm.
Input 0 V
0 V connection for supplying the internal
electronic circuits (from "–" output of the
power supply)
0.22 to 4 mm
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
Note: The 0 V of the loads must be supplied directly to the power supply by
means of separate lines !
Output
1, 2, 3, 4
Outputs of the diagnosis module for
connecting the load circuits
0.22 to 4 mm
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
13, 14
Common signaling contact
0.22 to 4 mm
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
Disconnection characteristic (typical)
:
Supply voltage > 20 V and the following power requirement for the branch concerned:
▪
0 % to 100 % of setting
►
No disconnection
▪
101 % to 130 % of setting
►
Disconnection after approx. 5 s
▪
> 130 % of setting
►
Current limited to approx. 130 %, disconnection after typ. 50 to 100 ms
Supply voltage dip < 20 V and the following power requirement for the branch concerned:
▪
> 100 % of setting
►
Immediate disconnection
Herausgegeben von:
SIMEA
Bereich IA SC
Siemensstraße 92
1210 Wien
Österreich
Published by:
SIMEA
IA SC Group
Siemensstraße 92
1210 Vienna
Austria
© Siemens AG Österreich 08/2013. All rights reserved
Liefermöglichkeiten und technische Änderungen vorbehalten
Availability and technical specifications subject to change without prior notice
Bestellnummer / Order number C98130-A7524-A1-7-7419
5,0sec
0,10sec
0,0sec
0,1sec
1,0sec
10,0sec
100,0sec
0%
20%
40%
60%
80% 100% 120% 140% 160%
I / Irated
t