background image

Product overview 

 

2.5 Operator controls and display elements 

 

CPU 1513R-1 PN (6ES7513-1RL00-0AB0) 

20

 

Equipment Manual, 05/2021, A5E42009333-AC 

2.5

 

Operator controls and display elements 

2.5.1

 

Front view of the CPU with closed front panel 

The figure below shows the front view of the CPU 1513R-1 PN. 

 

 

LEDs for the current operating state and diagnostic status of the CPU 

 

Display 

 

Control keys 

Figure 2-3 

View of the CPU 1513R-1 PN (with front panel) - front 

 

 

 

Note 
Temperature range for display 

To increase its service life, the display switches off at a temperature below the permitted 

operating temperature of the device. When the display cools down, it automatically switches 

itself on again. When the display is switched off, the LEDs continue to show the status of the 

CPUs. 
You can find additional information on the temperatures at which the display switches itself 

on and off in the Technical specifications (Page 33). 

 

Summary of Contents for 6ES7513-1RL00-0AB0

Page 1: ......

Page 2: ...6ES7513 1RL00 0AB0 Equipment Manual 05 2021 A5E42009333 AC Preface S7 1500R H Documentation Guide 1 Product overview 2 Connecting 3 Interrupts diagnostics error messages and system events 4 Technical specifications 5 Dimension drawing A ...

Page 3: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Page 4: ... enables you to commission the CPU 1513R 1 PN Conventions STEP 7 In this documentation STEP 7 is used as a synonym for all versions of the configuration and programming software STEP 7 TIA Portal Please also observe notes marked as follows Note A note contains important information on the product described in the documentation on the handling of the product or on the section of the documentation t...

Page 5: ...uous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used Use of product versions that are no longer supported and failure to apply the latest updates may increase customers exposure to cyber threats To stay informed about product updates subscribe to the Siemens Industrial Secu...

Page 6: ...Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation TIA and Totally Integrated Power TIP You can find catalogs for all automation and drive products on the Internet https mall industry siemens com ...

Page 7: ...roperties 15 2 4 Firmware functions 18 2 5 Operator controls and display elements 20 2 5 1 Front view of the CPU with closed front panel 20 2 5 2 Front view of the CPU without front panel 22 2 5 3 Rear view of the CPU 23 2 6 Mode selector 24 3 Connecting 25 3 1 Terminal assignment 25 4 Interrupts diagnostics error messages and system events 28 4 1 Status and error display of the CPU 28 5 Technical...

Page 8: ...rogramming Device information Product manuals contain a compact description of the module specific information such as properties wiring diagrams characteristics and technical specifications General information The function manuals contain detailed descriptions on general topics regarding the redundant S7 1500R H system e g diagnostics communication You can download the documentation free of charg...

Page 9: ...6630375 mySupport With mySupport your personal workspace you make the best out of your Industry Online Support In mySupport you can save filters favorites and tags request CAx data and compile your personal library in the Documentation area In addition your data is already filled out in support requests and you can get an overview of your current requests at any time You must register once to use ...

Page 10: ...d S1 devices PROFINET function manual http support automation siemens co m WW view en 49948856 MRP interconnection The MRP interconnection procedure is an extension of MRP MRP interconnection enables the redundant coupling of 2 or more rings with MRP in PROFINET networks MRP interconnection offers the following advantages When setting up redundant network topologies there is no limitation to the m...

Page 11: ...nchronization of the two R H CPUs is no longer possible redundantly S7 1500R H System Manual https support industry siemens com c s ww en view 109754833 RH_CTRL instruction As of FW version V2 9 the RH_CTRL instruction supports additional functions Request SYNCUP Switch primary CPU to STOP mode only in RUN Redundant system state Switch backup CPU to STOP mode Instructions for recipe phases As of F...

Page 12: ...program code with the help of breakpoints Localization of logic errors step by step Simple and quick analysis of complex programs prior to actual commissioning Recording of current values within individual executed loops Using breakpoints for program validation is also possible in SCL or STL networks within LAD FBD blocks PID controller PID controllers are built into all R H CPUs as standard PID c...

Page 13: ... PN 6ES7513 1RL00 0AB0 12 Equipment Manual 05 2021 A5E42009333 AC Additional information You can find an overview of all new functions improvements and revisions in the respective firmware versions on the Internet https support industry siemens com cs ww en view 109478459 ...

Page 14: ...wo SIMATIC memory cards PROFINET cable redundancy connections PROFINET ring IO devices Load power supply optional You mount the CPUs on a common mounting rail or spatially separated on two separate mounting rails You connect the two CPUs and the IO devices in a PROFINET ring via the PROFINET cable Optional load current supply First CPU Mounting rail with integrated DIN rail profile Second CPU PROF...

Page 15: ...control primary CPU The other CPU takes on the role of the following CPU backup CPU The assigned role of the CPUs can change during operation Synchronization of all relevant data between primary CPU and backup CPU ensures fast switching between CPUs in the event of a primary CPU failure If the primary CPU fails the backup CPU retains control of the process as the new primary CPU at the point of in...

Page 16: ...anual 05 2021 A5E42009333 AC 15 2 3 Hardware properties Article number 6ES7513 1RL00 0AB0 View of the module The figure below shows the CPU 1513R 1 PN Figure 2 2 CPU 1513R 1 PN Note Protective film Note that there is a removable protective foil on the display when the CPUs are delivered ...

Page 17: ...ltage The 24 V DC supply voltage is fed via a 4 pin plug located on the front of the CPU Section Connecting Page 25 Redundant System S7 1500R H https support industry siemens com cs ww en view 109754833 System Manual PROFINET IO PROFINET IO interface X1 P1 R and X1 P2 R The CPU has an X1 interface with two ports X1 P1 R and X1 P2 R The PROFINET IO interface X1 default P1 R is used to set up the PR...

Page 18: ...a switch in the PROFINET ring Make an Industrial Ethernet connection via the switch H Sync Forwarding H Sync Forwarding enables a PROFINET device with MRP to forward synchronization data synchronization frames of an S7 1500R redundant system only within the PROFINET ring In addition H Sync Forwarding forwards the synchronization data even during reconfiguration of the PROFINET ring H Sync Forwardi...

Page 19: ...ments However saving the measurements to the SIMATIC memory card is not supported Function manual Using the trace and logic analyzer function https support industry siemens co m cs ww en view 64897128 PROFINET IO System redundancy S2 IO Devices with S2 system redundancy enable uninter rupted operation during a primary backup switchover If the role of the CPUs changes the new primary CPU takes over...

Page 20: ...uring and position detection TO_BasicPos control of a SINAMICS drive SSI_Absolute_Encoder control of position detection and measuring function of the TM PosInput tech nology module STEP 7 online help Security Integrated Know how protection The know how protection protects user blocks against unauthorized access and modifications Redundant System S7 1500R H https support industry siemens co m cs ww...

Page 21: ... of the CPU Display Control keys Figure 2 3 View of the CPU 1513R 1 PN with front panel front Note Temperature range for display To increase its service life the display switches off at a temperature below the permitted operating temperature of the device When the display cools down it automatically switches itself on again When the display is switched off the LEDs continue to show the status of t...

Page 22: ...e front panel to protect the SIMATIC memory card and the mode selector of the CPU against unauthorized access You can attach a security seal or a padlock with a hoop diameter of 3 mm to the front panel Figure 2 4 Locking latch on the CPU In addition to the mechanical lock you can also block access to a password protected CPU on the display local lock and assign a password for the display You can f...

Page 23: ...or controls and connection elements of the CPU 1513R 1 PN LEDs for the current operating state and diagnostic status of the CPUs Display connector Slot for the SIMATIC memory card Mode selector LEDs for the 2 ports of the PROFINET interface X1 MAC address of the X1 interface PROFINET IO interface X1 with 2 ports Connector for power supply Fastening screw Figure 2 5 View of the CPU 1513R 1 PN witho...

Page 24: ...ment Manual 05 2021 A5E42009333 AC 23 2 5 3 Rear view of the CPU The figure below shows the connection elements on the rear of the CPU 1513R 1 PN Shield contact surface Plug in connection for power supply Plug in connection for backplane bus Fastening screw Figure 2 6 View of the CPU 1513R 1 PN rear ...

Page 25: ...shows the position of the switch and the corresponding meaning Table 2 1 Mode switch settings Position Meaning Explanation RUN RUN operating state The CPU has permission to go to RUN STOP STOP operating state The CPU does not have permission to go to RUN MRES Memory reset Position for CPU memory reset Reference You can find a brief overview of the various operating states and system states in the ...

Page 26: ...nal names and the descriptions of the pin assignment of the 24 V DC supply voltage Table 3 1 Pin assignment 24 V DC supply voltage View Signal name 1 Description Connector 1 1L 24 V DC of the supply voltage 2 1M Ground of the supply voltage 3 2M Ground of the supply voltage for loop through 2 4 2L 24 V DC of the supply voltage for loop through 2 1 1L and 2L as well as 1M and 2M are bridged interna...

Page 27: ... addresses CPU 1513R 1 PN has a PROFINET interface with two ports for each CPU The PROFINET interface itself has a MAC address and each of the two PROFINET ports has its own MAC address There are a total of six MAC addresses for the two CPUs of the CPU 1513R 1 PN The MAC addresses of the PROFINET ports are needed for the LLDP protocol for example for the neighborhood discovery function The number ...

Page 28: ...nterface X1 port 1 Display PN X1 P2 R PROFINET interface X1 port 2 Mode selector RUN STOP MRES L 24 V DC supply voltage Electronics M Ground PROFINET 2 port switch R S RUN STOP LED yellow green Backplane bus connection connection to backplane bus not configurable ER ERROR LED red Internal supply voltage MT MAINT LED yellow Supply of the 24 V DC supply voltage X80 X1 P1 X1 P2 LED Link TX RX Figure ...

Page 29: ...unction manual and in the system manual Redundant System S7 1500R H https support industry siemens com cs ww en view 109754833 You can find additional information on the topic of Operating states and system states as well as various failure scenarios in the system manual for S7 1500R H Redundant System https support industry siemens com cs ww en view 109754833 LED display The figure below shows th...

Page 30: ...displaying the current operating state and diagnostics status RUN STOP LED ERROR LED MAINT LED The LEDs indicate the operating state of the respective CPU within the redundant system Operating states describe the behavior of a single CPU at a specific time The combination of the operating states of the CPUs forms the system state The following figure shows the possible operating states of the CPUs...

Page 31: ...isplaying the current operating state and diagnostics status Note LED patterns of the redundant system S7 1500R Note that it is not always possible to Determine the state of the CPU from the signal pattern Determine the state of the other CPU from the signal pattern The Meaning column only shows a possible typical cause To investigate the cause of the signal pattern use the diagnostic buffer and i...

Page 32: ...LED off LED lit yellow The primary CPU is in operating state STARTUP The backup CPU is in operating state SYNCUP The backup CPU has not yet been restarted for SYNCUP during this phase LED flashes yellow LED off LED off The CPU performs a warm restart LED lit green LED off LED lit yellow Maintenance demanded for the plant You need to check replace the affected hardware within a short period of time...

Page 33: ...tween the PROFINET interface of the PROFINET device and the communication partner No data is currently being sent received via the PROFINET interface There is no LINK connection The redundancy connections were interrupted Flashes green The CPU performs an LED flash test Illuminated green There is an Ethernet connection between the PROFINET interface of your PROFINET device and a communication part...

Page 34: ...chronous mode No Engineering with STEP 7 TIA Portal configurable integrated from version V17 FW V2 9 V16 FW V2 8 V15 1 FW V2 6 Display Screen diagonal cm 3 45 cm Control elements Number of keys 6 Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains v...

Page 35: ...elements total 4 000 Blocks OB FB FC DB and UDTs DB Number range Number range 1 to 59 999 Size max 1 5 Mbyte For non optimized block accesses the max size of the DB is 64 KB FB Number range 0 65 535 Size max 300 kbyte FC Number range 0 65 535 Size max 300 kbyte OB Size max 300 kbyte Number of free cycle OBs 100 Number of time alarm OBs 20 Number of delay alarm OBs 20 Number of cyclic interrupt OBs...

Page 36: ... Retentive data area incl timers counters flags max 128 kbyte Flag Size max 16 kbyte Number of clock memories 8 8 clock memory bit grouped into one clock memory byte Data blocks Retentivity adjustable Yes Retentivity preset No Local data per priority class max 64 kbyte max 16 KB per block Address area Number of IO modules 2 048 max number of modules submodules I O address area Inputs 32 kbyte All ...

Page 37: ...ter Number 16 Clock synchronization supported Yes on Ethernet via NTP Yes Interfaces Number of PROFINET interfaces 1 1 Interface Interface types RJ 45 Ethernet Yes X1 Number of ports 2 integrated switch Yes Protocols IP protocol Yes IPv4 PROFINET IO Controller Yes PROFINET IO Device No SIMATIC communication Yes Only Server Open IE communication Yes Web server No Media redundancy Yes PROFINET IO Co...

Page 38: ...rconnection supported Yes as MRP ring node according to IEC 62439 2 Edition 3 0 MRPD No Switchover time on line break typ 200 ms PROFINET MRP Number of stations in the ring max 50 Only 16 are recommended however SIMATIC communication PG OP communication Yes encryption with TLS V1 3 pre selected S7 routing No S7 communication as server Yes S7 communication as client No Open IE communication TCP IP ...

Page 39: ...ag or GRAPH Number of loadable program messages in RUN max 2 500 Number of simultaneously active program alarms Number of program alarms 300 Number of alarms for system diagnostics 100 Test commissioning functions Joint commission Team Engineering No Status block Yes up to 8 simultaneously Single step No Number of breakpoints 8 Breakpoints are only supported in RUN Solo status Status control Statu...

Page 40: ...th integrated optimization for valves PID Temp Yes PID controller with integrated optimization for temperature Counting and measuring Yes High speed counter No Standards approvals certificates Suitable for safety functions No Ambient conditions Ambient temperature during operation horizontal installation min 0 C horizontal installation max 60 C Display 50 C at an operating temperature of typically...

Page 41: ...rd for display Yes Protection level Write protection Yes Protection level Read write protection Yes Protection level Complete protection Yes Cycle time monitoring lower limit adjustable minimum cycle time upper limit adjustable maximum cycle time Dimensions Width 35 mm Height 147 mm Depth 129 mm Weights Weight approx 430 g General technical specifications You can find information on the general te...

Page 42: ...This section contains the dimensional drawing of the module on the mounting rail as well as a dimensional drawing with the front panel open Keep to the dimensions when installing in cabinets control rooms etc Dimension drawings of the CPU 1513R 1 PN Figure A 1 Dimension drawing of the CPU 1513R 1 PN front and side view ...

Page 43: ...Dimension drawing A 1 Dimension drawing CPU 1513R 1 PN 6ES7513 1RL00 0AB0 42 Equipment Manual 05 2021 A5E42009333 AC Figure A 2 Dimension drawing of the CPU 1513R 1 PN side view with front panel open ...

Reviews: