Figure 9-18
X204 Coupling Configuration
"Coupling Mode"
Here you can set the coupling mode between HSR and the remaining network.
Coupling Mode
Meaning
HSR SAN Mode
The HSR ring is connected with Standard Ethernet end devices
or network segments (default).
Non Redundant HSR PRP coupling
Setting with non-redundant HSR<->PRP coupling. P1/A is con‐
nected with LAN A, P2/B with LAN B of a PRP network.
Redundant HSR PRP coupling, LAN A
Setting with redundant HSR<->PRP coupling. P1/A is connec‐
ted with LAN A of a PRP network. P2/B is open and may not be
used.
Redundant HSR PRP coupling, LAN B
Setting with redundant HSR<->PRP coupling. P1/B is connec‐
ted with LAN B of a PRP network. P1/A is open and may not be
used.
"NetID"
Here you can set the network ID of the connected PRP network. The valid value range is 1 to 6.
The NetID is used to distinguish between frames from different redundant PRP networks in an
HSR ring. It is not relevant in "HSR SAN Mode".
Functional description and configuration using Web Based Management
9.8 The "X200" menu
SCALANCE X-200RNA
Operating Instructions, 04/2022, C79000-G8976-C342-07
109