Settings in WBM
You specify the functionality of the devices SCALANCE X204RNA
①
to
④
relating to the
coupling of the two rings on the WBM page X200 > Coupling Configuration. You need to
configure the following parameters:
• Coupling Mode
• NetID
Configuration of the "Coupling Mode" parameter
Setting for device
①
and
③
Redundant HSR PRP coupling, LAN A (The port P2/B is open and must not be used.)
Setting for device
②
and
④
Redundant HSR PRP coupling, LAN B (The port P1/A is open and must not be used.)
Configuration of the "NetID" parameter
The network ID of the PRP network is specified with this parameter. The valid range of values is
1 to 6. The SCALANCE X204RNA devices between the two rings belong to the same PRP network,
therefore you need to set the same NetID for all devices
①
to
④
.
Network topologies and redundancy
4.3 HSR-PRP coupling
SCALANCE X-200RNA
Operating Instructions, 04/2022, C79000-G8976-C342-07
27