Properties
SCALANCE X204RNA
SCALANCE X204RNA EEC
Testing to IEC 61850-3
-
●
Testing to IEEE 1613
-
●
Note
PROFINET controllers can communicate with PROFINET devices via the HSR and PRP network
(PROFINET IO and RT). In this case all PROFINET devices (controllers and devices) must either be
capable of HSR or PRP themselves or must be connected to the HSR ring or to the PRP network
via a RedBox.
Within a PRP network (A or B), PROFINET controllers and devices can also communicate with
each other as SANs (PROFINET IO, RT and IRT). A direct PROFINET communication relationship
between DANPs and SANs or DANHs and SANs is not supported.
Table 5-1
Possible connections
Fast Ethernet 100 Mbps
SCALANCE X204RNA
SCALANCE X204RNA EEC
TP (RJ‑45)
4
2+2
Fiber
multimode
(duplex LC)
-
2 x SFP modules SFP991-1
multimode glass up to 3 km
6GK5991-1AD00-8AA0
Fiber
single mode
(duplex LC)
-
2 x SFP modules SFP991-1LD
monomode glass up to 26 km
6GK5991-1AF00-8AA0
Fiber
single mode
(duplex LC)
-
2 x SFP modules SFP991-1LH+
monomode glass up to 70 km
6GK5991-1AE00-8AA0
Standard Ethernet ports / PRP
ports
P1/A, P2/B
P1/A, P2/B
HSR ports
HSR 1, HSR 2
HSR 1, HSR 2
Note
TP connectors of SCALANCE X204RNA EEC
The SCALANCE X204RNA EEC has 2 RJ-45 ports to which you can connect two standard Ethernet
or PRP end devices/network structures without HSR capability.
The SCALANCE X204RNA EEC also has 2 RJ-45 ports and 2 SFP slots. These connection options
communicate with each other; in other words only one connector is ever active. If an SFP module
is inserted, the corresponding RJ-45 jack is disabled.
With these connector options, you can connect the device to an HSR ring.
Device description
5.1 Functions
SCALANCE X-200RNA
32
Operating Instructions, 04/2022, C79000-G8976-C342-07