WARNING
The SCALANCE X204RNA is designed for operation with safety extra-low voltage (SELV).
This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/
VDE0805 can be connected to the power supply terminals.
Measures must be taken to prevent transient overvoltages of more than 40% of the rated
voltage. This is the case if the devices are operated exclusively with SELV (Safety Extra Low
Voltage).
The power supply unit for the SCALANCE X204RNA power supply must meet NEC Class 2, as
described by the National Electrical Code(r) (ANSI/NFPA 70).
The power of all connected power supply units must total the equivalent of a power source with
limited power (LPS limited power source).
If the device is connected to a redundant power supply (two separate power supplies), both
must meet these requirements.
The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low voltage
(SELV), 24 VDC).
Never operate the SCALANCE X204RNA (PRP and HSR) with AC voltage or DC voltage higher
than 28.8 V DC.
24 VDC power supply
NOTICE
If the SCALANCE X204RNA is supplied over long 24 V power supply lines or networks,
measures are necessary to prevent interference by strong electromagnetic pulses on the
supply lines. These can result, for example, due to lightning or switching of large
inductive loads.
One of the tests used to attest the immunity of the SCALANCE X204RNA to electromagnetic
interference is the "surge immunity test" according to EN61000-4-5. This test requires
overvoltage protection for the power supply lines. A suitable device is, for example, the Dehn
Blitzductor BVT AVD 24 V type no. 918 422 or a comparable protective element.
Manufacturer: DEHN+SÖHNE GmbH+Co.KG, Hans-Dehn-Str.1, Postfach 1640, D-92306
Neumarkt, Germany.
Connecting up
7.2 Power supply
SCALANCE X-200RNA
74
Operating Instructions, 04/2022, C79000-G8976-C342-07