r040
Display of limitations:
Representation on operator panel (PMU):
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON:
Corresponding limitation is reached
Segment OFF:
Corresponding limitation is not reached
Segment or bit
0
α
W limit (field) reached (P251)
1
Negative current limit (field) reached (K0274)
2
α
W limit (armature) reached (
α
W acc. to P151
for continuous current, 165° for discontinuous current)
3 ....... Negative current limit (armature) reached (K0132)
4 ....... Negative maximum speed reached (P513)
Speed limiting controller responds (B0201)
5 ....... Negative torque limit reached (B0203)
6 ....... Neg. limitation at ramp generator output reached (K0182)
7 ....... Neg. limitation at ramp generator input reached (K0197)
8
.......
α
G limit (field) reached (P250)
9 ....... Positive current limit (field) reached (K0273)
10
.......
α
G limit (armature) reached (P150)
11 ....... Positive current limit (armature) reached (K0131)
12 ....... Positive maximum speed reached (P512)
Speed limiting controller responds (B0201)
13 ....... Positive torque limit reached (B0202)
14 ....... Pos. limitation at ramp generator output reached (K0181)
15 ....... Pos. limitation at ramp generator input reached (K0196)
Note: This parameter has the same bit assignments as connector K0810.
Ind:
None
Type: V2
P052 = 3
Connector and binector displays
r041
(G121)
High-resolution connector display:
i001: Display of connector selected in P042.01
i002: Display of connector selected in P042.02
The display value is filtered with a time constant of 300ms (see Section 8,
Sheet G121)
-200.00 to 199.99
[%]
0.01%
Ind: 2
Type: I2
P052 = 3
P042
*
(G121)
High-resolution connector display:
i001: Selection of connector to be displayed in r041.01
i002: Selection of connector to be displayed in r041.02
The display value is filtered with a time constant of 300ms (see Section 8,
Sheet G121)
All connector
numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Online
r043
(G121)
Connector display:
i001: Display of connector selected in P044.01
i002: Display of connector selected in P044.02
i003: Display of connector selected in P044.03
i004: Display of connector selected in P044.04
i005: Display of connector selected in P044.05
i006: Display of connector selected in P044.06
i007: Display of connector selected in P044.07
-200.0 to 199.9
[%]
0.1%
Ind: 7
Type: I2
P052 = 3
P044
*
(G121)
Connector display:
i001: Selection of connector displayed in r043.01
i002: Selection of connector displayed in r043.02
i003: Selection of connector displayed in r043.03
i004: Selection of connector displayed in r043.04
i005: Selection of connector displayed in r043.05
i006: Selection of connector displayed in r043.06
i007: Selection of connector displayed in r043.07
All connector
numbers
1
Ind: 7
FS=0
Type: L2
P052 = 3
P051 = 40
Online
r045
(G121)
Binector display:
i001: Display of binector selected in P046.01
i002: Display of binector selected in P046.02
i003: Display of binector selected in P046.03
i004: Display of binector selected in P046.04
0 to 1
Ind: 4
Type: O2
P052 = 3