Fault Code
Cause
Corrective Action
Control board fault.
Disconnect the inverter from the input power supply
Parameter P25 set above
Change parameter P25, P08 or P07.
Parameter P26 set above
Change parameter P26, P08 or P07.
Figure 5: Fault Code Table (Sheet 2 of 2)
and reconnect.
maximum frequency P08 or below
minimum frequency P07.
maximum frequency P08 or below
minimum frequency P07.
Parameter P27 set above
Change parameter P27, P08 or P07.
maximum frequency P08 or below
minimum frequency P07.
Inverter externally tripped via
Clear external trip on X11.4 and restart the inverter.
X11.4 input.
Parameter P28 set above
Change parameter P28, P08 or P07.
maximum frequency P08 or below
minimum frequency P07.
If a fault indication has been observed and the corrective action implemented, the inverter can be reset by applying
a STOP (low) signal to the run/stop input (terminal X11.3) followed by a RUN (high) signal to the same input.
Alternatively, the incoming mains voltage can be switched off and then switched on again.
5.5 Fault Relay
A single pole changeover relay is provided to indicate a fault. It is normally energised when the inverter is powered
and operating or stopped. If a fault condition occurs, the relay will be de–energised. The contacts of the relay are
connected to terminals X11.19 (normally open, de–energised), X11.20 (common) and X11.21 (normally closed,
de–energised) on the control board.
Summary of Contents for 6SE2101-1AA01
Page 5: ...English vi Siemens plc 1993 This page intentionally blank ...
Page 11: ...English 2 2 Siemens plc 1993 This page intentionally blank ...
Page 53: ...English 7 18 Siemens plc 1993 This page intentionally blank ...
Page 59: ...Deutsch vi Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Page 65: ...Deutsch 2 2 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Page 107: ...Deutsch 7 18 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...