Once steps (1) to (3) have been performed, P04 can be changed to match the requirements of the application.
NOTE
Speed control only operates in one direction of rotation – negative values of the actual speed feedback signal on
terminal X11.12 are not permitted.
6.2.2 Speed Control Operation
Stop the inverter and adjust the slip limit (P35) to 10.0 (unless the application requires the slip to be limited to a
lower value). Set the required frequency to a value in the middle of the operating range (i.e. approximately half way
between the minimum and maximum frequencies required in operation). Set the inverter to run and increase the
setting of P32 gradually until the motor speed starts to oscillate. Reduce the value of P32 until a stable speed is
obtained.
6.2.3 Speed Control Optimisation
If it is not possible to achieve stable operation with P32 set to a value of greater than 10, there must be excessive
noise on the feedback signal. It may be possible to filter out this noise by increasing the setting of the sampling rate
parameter (P36). If this fails then the feedback signal should be shielded and, in extreme cases, smoothed using
suitable capacitors.
Check the performance of the speed regulation. If the speed regulation is satisfactory when the load on the motor
changes then no further adjustments are required. However, the integral term and differential term parameters
(P33 and P34 respectively) allow further adjustments to be made to the control loop to compensate for delay and/or
lead terms in the motor and its associated speed sensor. This can provide better speed regulation in certain
systems.
Reducing the value of the proportional gain term will normally give more stable operation but with slightly degraded
speed–holding performance.
The slip limit parameter (P35) can be used to limit the maximum permissible deviation between the instantaneous
value of actual frequency and the output frequency.
6.2.4 Slip Limit (P35)
The slip limit parameter (P35) allows the difference between the actual frequency (from the tachometer) and the
inverter output frequency to be limited to a maximum level. This may be used to prevent motor stalling under
overload conditions.
6.2.5 Sample Rate (P36)
This parameter allows the rate at which the actual frequency value used by the speed regulator is updated to be
changed in 30 ms increments. When P36 is set to 001, the value is updated every 30 ms; when it is set to 002 it is
updated every 60 ms, etc.
Longer sample rates may be required in applications where electrical noise is present on the analogue feedback
signal or where the value of the analogue signal only responds slowly to changes in inverter/motor frequency.
Summary of Contents for 6SE2101-1AA01
Page 5: ...English vi Siemens plc 1993 This page intentionally blank ...
Page 11: ...English 2 2 Siemens plc 1993 This page intentionally blank ...
Page 53: ...English 7 18 Siemens plc 1993 This page intentionally blank ...
Page 59: ...Deutsch vi Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Page 65: ...Deutsch 2 2 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Page 107: ...Deutsch 7 18 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...