Start-Up
09.02
4-74
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
Bit 12 bis Bit 15 enthalten die
Auftragskennung
bzw. die dazugehörende
Antwortkennung
entsprechend der
folgenden Liste:
Response identifier
Request
identifier
Meaning
positive negative
0 No
request 0
1
Request parameter value (word or double word)
1 or 2
2
Modify parameter value (word)
1
3
Modify parameter value (double word)
2
4
Request descriptive element
3
5 Reserved -
6
Request parameter value (array) (word or double word)
4 or 5
7
Modify parameter value (array - word)
4
8
Modify parameter value (array-double word)
5
9
Request number of array elements
6
10 Reserved -
11
Modify parameter value (array-double word) and store in EEPROM
5
12
Modify parameter value (array-word) and store in EEPROM
4
13
Modify parameter value (double word) and store in EEPROM
2
14
Modify parameter value (double word) and store in EEPROM
1
15 Request
text 15
7 or 8
If the common rectifier has been unable to process the request, it does not return the associated response
identifier, but
error identifier
7 (or 8) instead.
In this case, an error code defining the error in more detail as shown in the following list is returned as a
parameter value:
Error code
Meaning
0
Illegal parameter number (PNU)
No PNU specified
1
Parameter value cannot be modified Visualization
parameter
2
Lower or upper value limit violated
3 Faulty
subindex
4
Parameter is not indexed (no array)
5
Parameter is not indexed (no array)
6
Parameter value can only be reset
7
Descriptive element cannot be modified
8
PPO Write (acc. to "Information Report") is not available
9
Parameter description is not available
10
Incorrect access level
11
No parameterizing enable (P927)
12
Keyword missing
Key parameter P051 incorrectly set
13
Text cannot be read cyclically
15 No
text
16
PPO Write missing
17
Incorrect operating state
19
Value cannot be read cyclically
101
Parameter number currently deactivated
102
Channel not wide enough
103
PKW number incorrect
Applies only to serial interfaces
104
Illegal parameter value
Applies to BiCo selection parameters