Parameter List
09.02
5-12
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.7 Control
r150 Control
Status
Status word of the control
6
7
14
15
2
3
10
11
0
1
8
9
4
5
12
13
Meaning of the individual segments
3
Rectifier current limit reached
4
Rectifier stability limit reached
11
Regerating current limit reached
12
Inverter stability limit reached
Segment bright: corresponding limit reached
Segment dark:
corresponding limit not reached
PNU=96Hex; Type=V2;
Scaling:
1Hex
=
∧
1
0 to 1818Hex
-
3/ BR
P160
Motor Curr Limit
Motoring current limit
The rectifier current is limited to the value set here
RDS parameter
PNU=0A0Hex; Type=O2; Scaling: 1Hex
=
∧
0.1
0.0 to 150.0% of
P075
[%]
4
150.0%
3/ ABR
3/ A
P161
**
Regen Curr Limit
Generating current limit
The regenerating current is limited to the value set here.
RDS parameter
PNU=0A1Hex; Type=I2; Scaling: 1Hex
=
∧
0.1
-150.0 to 0.0% of
P075
[%]
4
-150.0%
3/ ABR
3/ A
P310
DC Curr Reg Gain
Proportional gain of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
PNU=136Hex; Type=O2; Scaling: 1Hex
=
∧
0.01
0.01 to 1.00
4
0.15
3/ BR
3/ BR
P311
DC Curr Reg Time
Integral-action (reset) time of the DC link current controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
PNU=137Hex; Type=O2; Scaling: 1Hex
=
∧
0.001
0.001 to 1.000
[s]
4
0.015
3/ BR
3/ BR
P313
DC Volts RegGain
Proportional gain of the DC link voltage controller
This parameter is automatically set when circuit identification takes place
(P052=21)
RDS parameter
PNU=139Hex; Type=O2; Scaling: 1Hex
=
∧
0.01
0.10 to 200.00
4
3.00
3/ BR
3/ BR