Parameter List
09.02
5-32
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
P694
*
CB/TB Act Values
Actual-value output over the serial interface of the CB and/or TB module
Defines which parameter is to be transferred at which telegram address.
Note:
Word 1 should be set for status word 1 (r552=r968)
If the value "0" is entered (factory settings from i002 to i016), the constant
value "0" is passed on.
i001 Word 01 of the (process data part of the) telegram
i002 Word 02 of the (process data part of the) telegram
...
i016 Word16 of the (process data part of the) telegram
PNU=2B6Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 999
16
i001=968
i002=0
. . .
i016=0
3/ BR
3/ B
P695
*
CB/TB TlgOFFTime
Telegram lag time of CB and TB
If no correct telegram is received within the parameterized time a fault trip is
set.
Monitoring is carried out at intervals of 20 ms, therefore it is only appropriate
to set values that are multiples of 20 ms.
Description for setting:
0:
no monitoring, no fault trip; must be parameterized for sporadic
(non-cyclic) telegrams, e. g. operator panel OP at serial comm.
interface 1.
PNU=2B7Hex; Type=O2; Scaling: 1Hex
=
∧
1 ms
0 to 6500
[ms]
-
20
3/ BR
3/ BR
P696
CB Parameter 1
Communication board parameter 1.
See manual of the used communication board.
Parameter is only needed if a communication board is reported (P090 or
P091 = 1)
The communication board checks, if the set value is valid. If the value is not
accepted, the fault message 80 is issued with fault value 5
PNU=2B8Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/ H
P697
CB Parameter 2
Communication board parameter 2
see P696
PNU=2B9Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/H
P698
CB Parameter 3
Communication board parameter 3
See P696
PNU=2BAHex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/ H
P699
CB Parameter 4
Communication board parameter 4
See P696
PNU=2BBHex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/ H
P700
CB Parameter 5
Communication board parameter 5
See P696
PNU=2BCHex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/ H
P701
CB Parameter 6
Communication board parameter 6
See P696
PNU=2BDHex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 65535
-
0
3/ HBR
3/ H